2.2 SAFETY PRECAUTIONS ON SERVICING

P
lease follow these warnings when to undertake the following when
servicing an appliance with R290.
2.2.1 Checks to the area
P
rior to beginning work on systems containing flammable refrigerants,
safety checks are necessary to ensure that the risk of ignition is minimized.
For repair to the refrigerating system, the following precautions shall be
complied with prior to conducting work on the system.
2.2.2 Work procedure
W
ork shall be undertaken under a controlled procedure so as to minimize
the risk of a flammable gas or vapor being present while the work is being
performed.
2.2.3 General work area
A
ll maintenance staff and others working in the local area shall be
instructed on the nature of work being carried out. Work in confined
spaces shall be avoided. The area around the work space shall be
sectioned off. Ensure that the conditions within the area have been made
safe by control of flammable material.
2.2.4 Checking for presence of refrigerant
T
he area shall be checked with an appropriate refrigerant detector prior to
and during work, to ensure the technician is aware of potentially
flammable atmospheres. Ensure that the leak detection equipment being
used is suitable for use with flammable refrigerants, i.e. no sparking,
adequately sealed or intrinsically safe.
2.2.5 Presence of fire extinguisher
I
f any hot work is to be conducted on the refrigeration equipment or any
associated parts, appropriate fire extinguishing equipment shall be
available to hand. Have a dry powder or CO2 fire extinguisher adjacent to
the charging area.
2.2.6 No ignition sources