Operators force adjustment at stroke arrival - If = 0, setting off (the force value on the stroke is calculated
automatically) - If ≠ 0, indicates the value (expressed in% of the max value ) of the force exerted on the stroke.
"Energy saving" mode: If=1 after 10sec of inactivity, the control panel turns the 24V outputs and the display
off that will be turned on at first command received (use recommended battery-powered and / or solar
panel).
Warning: when "Energy saving" is enabled, SAS function is not available.
Warning: when "Energy saving" is enabled, only the stabilized output 24V_ST must be used to power
accessories.
Electric-lock output operating: If=0 "boost" output for electric-lock art.110 power supply, If=1 24V output
controlled by the ELOCK_IN input as pulsed mode,If=2 24V output controlled by the ELOCK_IN input as
step-by-step mode, If=3 electro-brake output for not self-locking operators, If=4 24V output for electric-lock
power supply via an external relay, If=5 24V output for electro-magnets power supply for barriers, If>5 24V
output controlled by the ELOCK_IN input as temporized mode (the set value indicates the switch-off delay in
seconds).
Run direction inversion: If=1 automatically reverses the outputs open/close of the operators and any opening/
closing limit switches inputs, avoiding having to manual change the wiring when installing the operator in an
inverted position.
Multiplier operations-counter: Multiply the number of operations after which the total operations-counter will
be updated.
To view the values, refer to the section "Visualisation of inputs and operations-counter status".
Maintenance Operations-counter: if = 0 reset the counter and disables the intervention request , if>
0 indicates the number of operations (x 500) to be made before the control panel executes a 4 second
additional pre-flash to indicate the need of maintenance.
i.g.: If P065 = 050, operations number = 50x500 = 25000 operations
Warning: Before you set a new value of the counter-manoeuvres maintenance, the same must be reset by
setting P065= 0 and only later P065 = "new value".
Selection of operating flashing light output: If=0 intermittent flashing light output;
If=1 Fixed flashing light output (for flashing lights with intermittent interior circuits).
SAFETY 1
SAFETY 2
Delay on limit switch detection: the operation is stopped after 1,5 sec from limit switch detection. When
during this delay a stop is detected, the operator is suddenly stopped
Adjustment of acceleration durability
Warning: if soft start is activated, the acceleration is deactivated indipendently from P070 value.
48
Operation of the SFT input: if = 0 safety edge always enabled, if = 1 safety edge enabled only
while closing, if = 2 safety edge enabled only while closing and before any movement, if = 3
safety edge enabled only when opening, if = 4 safety edge enabled only while opening and
before any movement; as for the obstacle detection with internal anti-crushing sensor, also the
activation of the inputs SFT1 and SFT2 causes the complete or partial reversal as set by P055
(duration of inversion on obstacles while opening, and P056 (duration of reversal on obstacle
while closing)