7 ADVANCED PROGRAMMING
Here are some added programming procedures relating to remotes memory management and advanced configuration of the control
inputs.
1 Deletion of memorized transmitters
1.1 Deletion of all transmitters
1. Scroll down the parameters until you visualize P004;
2. Confirm by pressing on the
3. When "
" is flashing, press the
onds;
4. Release the
key as soon as "
5. All memorized transmitters have been deleted (display
shows again P004).
1.2 how to search and delete a transmitter
1. Scroll down the parameters until you visualize P006;
2. Confirm by pressing on the
3. By pressing on
and
, keys, select the transmitter you
want to delete (eg.
);
4. When "
" flashes, confirm the deletion by pressing
the
key for a few seconds;
5. Release the
key when appears "
6. The selected transmitter is deleted (display shows again
P006).
2 Restoring default parameters
2.1 Restoring operating parameters
1. Scroll through the parameters with the buttons
until the display shows P007;
2. Confirm by pressing on the
3. When "
" is flashing, press the
seconds;
4. Release the
key as soon as "
All the default values are restored except for the para-
meters from P016 to P022 and P076 to P098 for the
configuration currently in use;
5. At the end of the operation display returns to P007.
Warning: After you restore the default parameters, you
must program the control panel again and adjust all ope-
rating parameters, in particular, remember to properly
set the operator configuration parameters. (P028 - P029
- P030).
Warning: For reversible motors with electro-brake, remem-
ber to set P062 = 3 at the end of the procedure.
2.2 Restoring "I/O" setting (Input/Output)
1. Scroll through the parameters with the buttons
until the display shows P010;
2. Confirm by pressing on the
3. When "
" is flashing, press the
seconds;
4. Release the
key as soon as "
All the default values only for the parameters from
P016 to P022 and from P076 to P098 are restored for
the configuration currently in use;
5. At the end of the operation display returns to P010.
key;
key for a few sec-
" stops flashing;
key;
";
and
key;
key for a few
" stops flashing;
and
key;
key for a few
" stops flashing;
39