AERASGARD
FSFTM - CO2 - Modbus
The room sensor and measuring transducer AERASGARD
measure the CO2 content, relative humidity and temperature of the air, and for setpoint adjustment. The measured values are queried via the
Modbus interface. The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). A digital, long-term
stable sensor is used for humidity and temperature measurement. Relative humidity [% r. H.] is the quotient of water vapour partial pressure divided
by the saturation vapour pressure at the respective gas temperature.
The in-wall sensor is mounted in high-quality panel switch programmes, ideally of the brands Gira, Berker, Merten, Jung, Siemens or Busch-Jaeger
(using in-wall adapters, no setpoint adjustment possible) either individually or in combination with light switches, socket outlets, etc. It is used in
non-aggressive, dust-free environments, in refrigeration, air conditioning and clean room technology, and in interior rooms, such as living rooms,
offices, hotels, etc.

TECHNICAL DATA

Power supply:
Power consumption:
Data points:
Bus protocol:
Signal filtering:
CARBON DIOXIDE (CO2)
Sensor, CO2:
Long-term stability:
Measuring range, CO2:
Measuring accuracy, CO2:
Temperaturedependence, CO2: ± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C (whichever is higher)
Pressure dependence:
Gas exchange:
Warm up time:
Response time:
HUMIDIT Y
Sensor:
Long-term stability:
Measuring range, humidity:
Operating range, humidity:
Deviation, humidity:
TEMPERATURE
Measuring range:
Deviation, temperature:
Mounting:
Electrical connection:
Ambient temperature:
Permitted humidity:
Medium:
Protection class:
Protection type:
Standards:
SWITCH PROGRAMME
Manufacturer:
Housing:
Type ⁄ WG02
Measuring Range
CO2
FSFTM-CO2-Modbus
0...5000 ppm
FSFTM-CO2-Modbus P
0...5000 ppm
Data points:
relative humidity [% r. H.], temperature [°C], CO2 content of the air [ppm] and setpoint potentiometer
®
FSFTM - CO2 - Modbus in the in-wall housing, optionally with potentiometer, is used to
24 V AC ⁄ DC (± 10 %)
< 4.4 W ⁄ 24 V DC ; < 6.4 VA ⁄ 24 V AC
relative humidity [% r.H.], temperature [°C],
CO2 content of the air [ppm]
as well as setpoint potentiometer
(no setpoint adjustment possible with Busch-Jaeger)
Modbus (RTU mode),
address range 0...247 selectable
4 s / 32 s
optical NDIR sensor
(non-dispersive infra-red technology),
with manual calibration (via zero button) and automatic calibration
< 2 % in 15 years
0...5000 ppm
typically ± 30 ppm ± 3 % of measured value
± 0.13 % ⁄ mm Hg
by diffusion
approx. 1 hour
< 2 minutes
digital humidity sensor with integrated temperature sensor,
low hysteresis, high long-term stability
± 1 % per year
0...100 % r. H.
0...95 % r. H. (non-precipitating air)
typically ± 3.0 % (20...80 % r. H.) at +25 °C, otherwise ± 5.0 %
0...+50 °C
typically ± 0.8 K at +25 °C
in-wall flush box Ø 55 mm
1.0 - 2.5 mm², via plug terminals
Storage –35...+85 °C; Operation 0...+50 °C
max. 90 % r.H., non-precipitating air
clean air and other non-aggressive, non-combustible gases
III (according to EN 60 730)
IP 20 (according to 60 529)
CE-conformity, electromagnetic compatibility according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU
GIRA System 55
(other switch programmes, manufacturers, colours as well as prices available upon request)
plastic,
the standard colour is pure glossy white (similar to RAL 9010)
(other colours are available upon request with colour variants
depending on the respective light switch programme)
Humidity
Temperature
0...100 % r. H.
0...100 % r. H.
Control
element
0...+50 °C
0...+50 °C
Potentiometer
10
Output
Item No.
Modbus
1501- 9226-6001- 162
Modbus
1501- 9226-6501- 282