G
®
AERASGARD
FSFTM - CO2 - Modbus | Telegrams
TELEGRAMS
Function 04 Read Input Register
Register
3x0001
CO2
3x0002
CO2
VOC
3x0003
3x0004
VOC
Temperature
3x0005
3x0006
Temperature
3x0007
Relative humidity
Relative humidity
3x0008
3x0009*
not assigned
not assigned
3x0010*
3x0011*
Potentiometer position
* only for device version with setpoint potentiometer
Function 05 Write Single Coil
Register
0x0001
Reset (Auto zero) CO2
0x0003
Automatic calibration (Automatic) CO2
Function 06 Write Single Register & Function 16 Write Multiple Register
Register
Offset CO2
4x0021*
4x0022*
not assigned
4x0023*
Offset temperature
Offset relative humidity
4x0024*
* only for device version with setpoint potentiometer
Function 08 Diagnostics
Sub Function
Parameter
Code
00
Echo of transmission data (Loopback)
01
Restart Modbus (Reset listen-only mode)
Activation listen-only mode
04
10
Delete counter
Counter bus telegrams
11
Counter communication errors
12
(Parity, CRC, frame errors, etc.)
13
Counter exception telegrams
Counter slave telegrams
14
15
Counter telegrams without answer
Function 17 Report Slave ID
Byte No.
Parameter
00
Number of bytes
01
Slave ID (device type)
Slave ID (device class)
02
03
Status
Version number (release)
04
Version number (version)
05
06
Version number (index)
Parameter
Sampling 4 s
Filtering 32 s
Sampling 4 s
Filtering 32 s
Sampling 4 s
Filtering 32 s
Sampling 4 s
Filtering 32 s
–
–
no filtering
Parameter
Parameter (display)
The following sub function codes are supported
Composition of answer telegram
Data Type
Signed 16 bit
350...5000
Signed 16 bit
350...5000
Signed 16 bit
0...1000
Signed 16 bit
0...1000
Signed 16 bit
0...500
Signed 16 bit
0...500
Signed 16 bit
0...1000
Signed 16 bit
0...1000
–
–
Signed 16 Bit
0...1000
Data Type
Bit 0
Bit 2
Data Type
Signed 16 Bit
–512...511
Signed 16 Bit
–512...511
Signed 16 Bit
–512...511
Signed 16 Bit
–512...511
Data Type
Answer
Echo data
Echo telegram
No answer
Echo telegram
Unsigned 16 bit
All valid bus telegrams
Unsigned 16 bit
Faulty bus telegrams
Unsigned 16 bit
Error counter
Unsigned 16 bit
Slave telegrams
Unsigned 16 bit
Broadcast messages (address 0)
Data Type
Answer
Unsigned 8 bit
6
Unsigned 8 bit
14 = AERSGARD
Unsigned 8 bit
60 = AERASGARD
Unsigned 8 bit
255 = RUN, 0 = STOP
Unsigned 8 bit
1...9
Unsigned 8 bit
1...99
Unsigned 8 bit
1
13
Value
Range
350...5000 ppm
350...5000 ppm
0.0...100.0 % VOC
0.0...100.0 % VOC
0.0...+50.0 °C
0.0...+50.0 °C
0.0...100.0 % r.H.
0.0...100.0 % r.H.
–
–
–
–
0.0...100.0 % r.H.
Value
Range
0 / 1
OFF - ON
0 / 1
OFF - ON
Value
Range
Offset
Offset
Offset
Offset
®
Modbus
®