Technical Data - S+S Regeltechnik HYGRASGARD RPFF Notice D'instruction

Masquer les pouces Voir aussi pour HYGRASGARD RPFF:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
®
HYGRASGARD
Quality product for HVAC sector, accuracy 3 % r.H.
The calibrateable pendulum room humidity and temperature sensor HYGRASGARD
humidity and temperature of air. It converts the measurands humidity and temperature into standard signals of 0 - 10 V or 4...20 mA and
is optional available with or without display. It has four switchable temperature ranges. Relative humidity (in % r. H.) is the quotient of water
vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature. HYGRASGARD
in non-aggressive dust-free ambiences in refrigeration, air conditioning, ventilation and clean room technology, hotels, technical rooms,
meeting rooms and convention centres. These measuring transducers are designed for exact detection of temperature and humidity.
A digital long-term stable sensor is used as measuring element for humidity and temperature measurement. Fine adjustment by the user
is possible. The sensor is appropriate for ceiling and duct installation, or for integrating it into equipment.

TECHNICAL DATA:

Power supply: .............................. 24 V AC (± 20 %) and 15 ... 36 V DC (± 10 %) for U variant
Power consumption: .................. < 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC
Sensors: ....................................... digital humidity sensor
Sensor protection: ..................... membrane filter, exchangeable
HUMIDITY:
Measuring range, humidity: ...... 0 ...100 % r. H.
Operating range, humidity: ....... 0 ... 95 % r. H. (without formation of dew)
Deviation, humidity: .................... ± 3 % r. H. (20...80 %) at +20 °C, otherwise ± 5 % r. H.
Output, humidity: ........................ 0 -10 V at U variant
TEMPERATURE:
Measuring range, temperature: ... multi-range switching (see table)
Operating range, temperature: ... - 35 ...+80 °C
Deviation, temperature: ............ ± 0.3 K (RPFF ⁄ RPFTF-U)
Output, temperature: ................ 0 -10 V or 4...20 mA
Ambient temperature: .............. storage - 25 ...+ 50 °C
Long-term stability: .................... ± 1 % per year
Electrical connection: ................ 2-, 3-, or 4-wire connection (see connecting diagram),
Cable length: ............................... 2 m, other lengths optional
Enclosure: .................................... plastic, material polyamide, 30 % glass-globe-reinforced,
Dimensions: ................................. RPFF ⁄ RPFTF:
Cable gland: ................................. M16, including strain relief
Protective tube: .......................... RPFF ⁄ RPFTF:
Protection class: ........................ III (according to EN 60 730)
Protection type:.......................... IP 65 (according to EN 60 529)
Standards: ................................... CE conformity,
Optional: ....................................... two-line display with illumination, 36 x15 mm (W x H),
RPFF ⁄ RPFTF, RPFF - 25 ⁄ RPFTF - 25
15 ... 36 V DC (± 10 %) for I variant (depending on working resistance)
with integrated temperature sensor,
dew-proof, small hysteresis, high long-term stability
RPFF ⁄ RPFTF: metal sinter filter
RPFF-25 ⁄ RPFTF-25: plastic sinter filter
(output corresponding to 0 -10 V or 4 ... 20 mA)
4 ... 20 mA at I variant, working resistance < 800 Ω,
see load resistance diagram
- 35 ...+35 °C; - 35 ...+75 °C; 0 ...+50 °C; 0 ...+80 °C
(output corresponding to 0 -10 V or 4 ... 20 mA)
± 0.5 K (RPFF ⁄ RPFTF-I) at 20 °C
operation - 5 ...+ 55 °C
0.14 - 1.5 mm² via terminal screws on circuit board
with quick-locking screws, colour pure white (similar RAL 9010)
72 x 64 x 39.4 mm
RPFF-25 ⁄ RPFTF-25:
108 x 70 x 73.5 mm
metal, L =100 mm + 25 mm, Ø =16 mm
RPFF-25 ⁄ RPFTF-25:
stainless steel, L =120 mm, Ø =18 mm
according to EMC directive 2004 ⁄ 108 ⁄ EC,
according to EN 61326-1: 2006,
according to EN 61326-2-3: 2006
for displaying ACTUAL temperature and ⁄ or ACTUAL humidity
®
RPFTF with membrane filter measures the relative
10
®
RPFTF is applied

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Hygrasgard rpftfHygrasgard rpff-25Hygrasgard rpftf-25

Table des Matières