S+S Regeltechnik AERASGARD RCO2 MODBUS Notice D'instruction

S+S Regeltechnik AERASGARD RCO2 MODBUS Notice D'instruction

Masquer les pouces Voir aussi pour AERASGARD RCO2 MODBUS:

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

D G F r
6003-4700-2017-000 34700-2017 V101 03/2017
RFTM - LQ - CO
AERASGARD
® 
D
Bedienungs- und Montageanleitung
Multifunktionaler Raumfühler bzw. Messumformer,
für Feuchte, Temperatur, Luftgüte (VOC) und CO
kalibrierfähig, mit Modbus-Anschluss
G
Operating Instructions, Mounting & Installation
Multifunctional room sensors and measuring transducers,
for humidity, temperature, air quality (VOC) and CO
calibratable, with Modbus connection
F
Notice d'instruction
Sonde d'ambiance (transmetteur) multifonctionnelle,
pour l'humidité, la température,
la qualité d'air (COV) et de teneur en CO
étalonnable, avec raccordement Modbus
r
Руководство по монтажу и обслуживанию
Мультифункциональный датчик для помещений ⁄ измерительный
преобразователь, для измерения влажности, температуры,
качества воздуха (VOC) и содержания CO
калибруемый, с подключением к шине Modbus
S+S REGELTECHNIK GMBH
PIRNAER STRASSE 20
90411 NÜRNBERG ⁄ GERMANY
FON +49 (0) 911 ⁄ 5 19 47- 0
FAX +49 (0) 911 ⁄ 5 19 47- 70
mail@SplusS.de
www.SplusS.de
- Modbus
2
- Gehalt,
2
content,
2
,
2
,
2
Herzlichen Glückwunsch!
Sie haben ein deutsches Qualitätsprodukt erworben.
Congratulations!
You have bought a German quality product.
Félicitations !
Vous avez fait l'acquisition d'un produit allemand de qualité.
Примите наши поздравления !
Вы приобрели качественный продукт, изготовленный в Германии.

Publicité

Table des Matières
loading

Sommaire des Matières pour S+S Regeltechnik AERASGARD RCO2 MODBUS

  • Page 1 Руководство по монтажу и обслуживанию Мультифункциональный датчик для помещений ⁄ измерительный преобразователь, для измерения влажности, температуры, качества воздуха (VOC) и содержания CO калибруемый, с подключением к шине Modbus S+S REGELTECHNIK GMBH Herzlichen Glückwunsch! Sie haben ein deutsches Qualitätsprodukt erworben. PIRNAER STRASSE 20 Congratulations! 90411 NÜRNBERG ⁄...
  • Page 2 D G F r RFTM - LQ - CO - Modbus AERASGARD ®  Maßzeichnung R CO - Modbus Dimensional drawing RLQ - CO - Modbus Plan coté RFTM - CO - Modbus Габаритный чертеж RFTM - LQ - CO - Modbus (Baldur 2) 32.6...
  • Page 3: Technische Daten

    ® AERASGARD RFTM - LQ - CO - Modbus Rev. 2017 - V21 DE Der wartungsfreien mikroprozessorgesteuerten Raumfühler mit Modbus- Anschluss, wahlweise mit ⁄ ohne Display, im formschönen Gehäuse aus Kunst- stoff, mit Schnappdeckel, Unterteil mit 4-Loch befestigung, dient zur Erfassung aller relevanten Messgrößen wie Luftfeuchtigkeit, Temperatur, - Konzentration sowie Luft qualität (VOC) in einem Gerät und ermöglicht somit die effektive Überwachung und Steuerung des gesamten Raumklimas.
  • Page 4 ® AERASGARD RFTM - LQ - CO - Modbus Rev. 2017 - V21 DE Anzeige Anzeige Standard alternative Ausgangsgrößen Standardmäßig werden im Display die Mess werte mit den Über die Modbusschnittstelle kann anstelle der Standard-Anzeige entsprechenden Einheiten zyklisch nacheinander angezeigt: eine alternative Ausgangs größe programmiert werden.
  • Page 5 ® AERASGARD RFTM - LQ - CO - Modbus | Konfiguration Rev. 2017 - V13 DE intro BUSADRESSE MODBUS Busadresse (binärcodiert, Wertigkeit 1 bis 247 einstellbar) DIP-Schalter [ A ] DIP 1 DIP 2 DIP 3 DIP 4 DIP 5 DIP 6 DIP 7 DIP 8...
  • Page 6: Table Des Matières

    ® AERASGARD RFTM - LQ - CO - Modbus | Konfiguration Rev. 2017 - V13 DE intro ANZEIGE IM DISPLAY Standardmäßig werden im Display die Mess werte mit den entsprechenden Einheiten zyklisch nacheinander angezeigt: -Gehalt in ppm, Luft qualität (VOC) in %, Temperatur in °C, relative Feuchte in % r.H. Über die Modbusschnittstelle kann anstelle der Standard-Anzeige eine alternative Ausgangs größe programmiert werden: -Gehalt in ppm, Luft qualität (VOC) in %, Temperatur in °C, relative Feuchte in % r.H.
  • Page 7 ® AERASGARD RFTM - LQ - CO - Modbus | Konfiguration ASCII-Code-Tabelle für Dot Matrix Anzeigebereich ASCII Sign ASCII Sign ASCII Sign ASCII Sign ASCII Sign Leer “ & < > ü ä Ä ö Ö Ü ° Nicht in der Tabelle aufgeführte ASCII-Zeichen bzw. Steuerzeichen werden als Leerzeichen dargestellt.
  • Page 8 ® AERASGARD RFTM - LQ - CO - Modbus | Telegramme TELEGRAMME Function 04 Read Input Register Register Parameter Data Type Value Range 3x0001 Abtastung 4 s Signed 16 Bit 350...5000 350...5000 ppm 3x0002 Filterung 32 s Signed 16 Bit 350...5000 350...5000 ppm 3x0003...
  • Page 9: Bit 0

    ® AERASGARD RFTM - LQ - CO - Modbus | Telegramme Function 05 Write Single Coil Register Parameter Data Type Value Range 0x0001 Reset (Autozero) CO2 Bit 0 0 / 1 OFF - ON 0x0002 Reset (Autozero) VOC Bit 1 0 / 1 OFF - ON 0x0003...
  • Page 10 ® AERASGARD RFTM - LQ - CO - Modbus | Installation Rev. 2015 - 1.0 DE intro Allgemeiner Aufbau Busstruktur MODBUS RTU-Master Passiver Aktiver Abzweig Abzweig RS-485 Leitungs- Leitungs- Stammleitung abschluss abschluss (Trunk-Kabel) Stichleitung (Drop-Kabel) Slave n Stichleitung: Mehrfachabzweigung n: Slave 1 Slave 2 kürzer 20m...
  • Page 11: Montage Und Installation

    Montage und Installation Die Geräte sind im spannungslosen Zustand anzuschließen. Der Hinweise zum mechanischen Ein- und Anbau: Der Einbau hat unter Berücksichtigung der einschlägigen, für den Mess ort Anschluss der Geräte darf nur an Sicherheitskleinspannung er folgen. gültigen Vorschriften und Standards (wie z. B. Schweiß vor schriften usw.) Folge schäden, welche durch Fehler an diesem Gerät entstehen, sind zu erfolgen.
  • Page 12: Wichtige Hinweise

    Wichtige Hinweise Als AGB gelten ausschließlich unsere sowie die gültigen „Allgemeinen Lieferbedingungen für Erzeugnisse und Leistungen der Elektro industrie“ (ZVEI Bedingungen) zuzüglich der Ergänzungsklausel „Erweiterter Eigentumsvorbehalt“. Außerdem sind folgende Punkte zu beachten: – Der Anschluss der Geräte darf nur an Sicherheitskleinspannung und im spannungslosen Zustand erfolgen. Um Schäden und Fehler am Gerät (z.B.
  • Page 14: Technical Data

    ® HYGRASGARD RFTM - LQ - CO - Modbus Rev. 2017 - V21 GB The maintenance-free microprocessor-controlled room sensor with Modbus connection with/without optional display, in elegant plastic housing, with snap-on lid, base with 4-hole attachment is an all-in-one device used for detecting all relevant measured values, such as humidity, temperature, CO concentration and air quality (VOC), thus enabling effective monitoring and control of the entire room climate.
  • Page 15 ® HYGRASGARD RFTM - LQ - CO - Modbus Rev. 2017 - V21 GB Display Display standard alternative output variables By default, the display indicates the following measurements The Modbus interface can be used to program an alternative output with the corresponding units cyclically and consecutively: variable instead of the standard display.
  • Page 16: Bus Address

    ® HYGRASGARD RFTM - LQ - CO - Modbus | Configuration Rev. 2017 - V14 GB intro BUS ADDRESS MODBUS Bus address (binary coded, value selectable from 1 to 247) DIP switch [ A ] DIP 1 DIP 2 DIP 3 DIP 4 DIP 5 DIP 6...
  • Page 17: Bit 1

    ® HYGRASGARD RFTM - LQ - CO - Modbus | Configuration READOUT IN THE DISPLAY By default, the display indicates the following measurements with the corresponding units cyclically and consecutively: content in ppm, air quality (VOC) in %, temperature in °C, relative humidity in % r.H. The Modbus interface can be used to program an alternative output variable instead of the standard display: content in ppm, air quality (VOC) in %, temperature in °C, relative humidity in % r.H.
  • Page 18 ® HYGRASGARD RFTM - LQ - CO - Modbus | Configuration ASCII Code Table for Dot Matrix Display Area ASCII Sign ASCII Sign ASCII Sign ASCII Sign ASCII Sign Blank “ & < > ü ä Ä ö Ö Ü °...
  • Page 19 ® HYGRASGARD RFTM - LQ - CO - Modbus | Telegrams TELEGRAMS Function 04 Read Input Register Register Parameter Data Type Value Range 3x0001 Sampling 4 s Signed 16 bit 350...5000 350...5000 ppm 3x0002 Filtering 32 s Signed 16 bit 350...5000 350...5000 ppm 3x0003...
  • Page 20 ® HYGRASGARD RFTM - LQ - CO - Modbus | Telegrams Function 05 Write Single Coil Register Parameter Data Type Value Range 0x0001 Reset (Auto zero) CO2 Bit 0 0 / 1 OFF - ON 0x0002 Reset (Auto zero) VOC Bit 1 0 / 1 OFF - ON...
  • Page 21 ® HYGRASGARD RFTM - LQ - CO - Modbus | Installation Rev. 2017 - V14 GB intro General layout of bus structure MODBUS RTU-Master Passive Active branch branch RS-485 Line Line Trunk line termination termination Stub line Slave n Stub line: Multiple branch n: Slave 1 Slave 2...
  • Page 22: Mounting And Installation

    Mounting and Installation Devices are to be connected under dead-voltage condition. Devices Notes regarding mechanical mounting and attachment: must only be connected to safety extra-low voltage. Consequential Mounting shall take place while observing all relevant regulations and damages caused by a fault in this device are excluded from warranty standards applicable for the place of measurement or liability.
  • Page 23 Important notes Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions. In addition, the following points are to be observed: –...
  • Page 25: Caractéristiques Techniques

    ® HYGRASGARD RFTM - LQ - CO - Modbus Rev. 2017 - V21 FR La sonde commandée par microprocesseur sans entretienavec raccordement Modbus, au choix avec / sans écran, dans un boîtier élégant en plastique, avec couvercle emboîté, partie inférieure avec 4 trous de fixation, sert à mesurer toutes les valeurs de mesure importantes, telles que l'humidité, la température, la concentration en CO ainsi que la qualité...
  • Page 26: Sonde D'ambiance Multifonctionnelle Pour L'humidité, La Température Et De Teneur En Co

    ® HYGRASGARD RFTM - LQ - CO - Modbus Rev. 2017 - V21 FR Affichage Affichage standard dimensions de sortie alternatives Par défaut, les valeurs de mesure suivantes sont affichées Via l'interface Modbus, l'affichage d'une dimension de sortie de manière cyclique, les unes après les autres dans l'écran alternative peut être programmée au lieu de l'affichage standard.
  • Page 27: Paramètres Du Bus

    ® HYGRASGARD RFTM - LQ - CO - Modbus | Configuration Rev. 2017 - V14 FR intro ADRESSE DU BUS MODBUS Adresse du bus (code binaire, valance réglable de 1 à 247) Interrupteur DIP [ A ] DIP 1 DIP 2 DIP 3 DIP 4 DIP 5...
  • Page 28: Affichage Sur L'écran

    ® HYGRASGARD RFTM - LQ - CO - Modbus | Configuration AFFICHAGE SUR L'ÉCRAN Par défaut, les valeurs de mesure suivantes sont affichées de manière cyclique, les unes après les autres dans l'écran avec les unités correspondantes : Teneur en CO , qualité...
  • Page 29 ® HYGRASGARD RFTM - LQ - CO - Modbus | Configuration Tableau des codes ASCII pour la zone d'affichage de la matrice de points ASCII Sign ASCII Sign ASCII Sign ASCII Sign ASCII Sign Espace “ & < > ü ä...
  • Page 30 ® HYGRASGARD RFTM - LQ - CO - Modbus | Télégrammes TÉLÉGRAMMES Function 04 Read Input Register Registre Paramètre Data Type Value Range 3x0001 Balayage 4 s Signed 16 Bit 350…5000 350...5000 ppm 3x0002 Filtrage 32 s Signed 16 Bit 350…5000 350...5000 ppm 3x0003...
  • Page 31 ® HYGRASGARD RFTM - LQ - CO - Modbus | Télégrammes Function 05 Write Single Coil Registre Paramètre Data Type Value Range 0x0001 Réinitialisation (Autozero) CO2 Bit 0 0 / 1 OFF - ON 0x0002 Réinitialisation (Autozero) COV Bit 1 0 / 1 OFF - ON 0x0003...
  • Page 32 ® HYGRASGARD RFTM - LQ - CO - Modbus | Installation Rev. 2017 - V14 FR intro Structure générale du bus MODBUS RTU-Master Raccord Raccord actif passif RS-485 Fin de ligne Fin de ligne Ligne principale (câble principal) Tronçon (câble de dérivation) Slave n Tronçon :...
  • Page 33: Montage Et Installation

    Montage et installation Les raccordements électriques doivent être exécutés HORS TENSION. Consignes pour l’installation mécanique : Veillez à ne brancher l’appareil que sur un réseau de très basse tension Effectuer le montage en tenant compte des dispositions et règles de sécurité. Nous déclinons toute responsabilité ou garantie au titre standards à...
  • Page 34: Généralités

    Généralités Seules les CGV de la société S+S, les « Conditions générales de livraison du ZVEI pour produits et prestations de l’industrie électronique » ainsi que la clause complémentaire « Réserve de propriété étendue » s’appliquent à toutes les relations commerciales entre la société S+S et ses clients. Il convient en outre de respecter les points suivants : –...
  • Page 36: Технические Данные

    ® HYGRASGARD RFTM - LQ - CO - Modbus Rev. 2017 - V21 RU Не нуждающийся в техническом обслуживании, управляемый микропроцессором датчик для помещений с возможностью подключения к шине Modbus, на выбор с дисплеем или без дисплея, в элегантном корпусе из пластика, с защелкивающейся крышкой, низом с четырьмя отверстиями, служит для измерения всех...
  • Page 37 ® HYGRASGARD RFTM - LQ - CO - Modbus Rev. 2017 - V21 RU Индикация Индикация (стандартная) альтернативных выходных величин В стандартном исполнении на дисплее поочередно и Используя шинный интерфейс, вместо стандартной индикации циклично отображаются следующие измеренные значения с можно запрограммировать отображение альтернативной выходной соответствующими...
  • Page 38 ® HYGRASGARD RFTM - LQ - CO - Modbus | Конфигурация Rev. 2017 - V14 RU intro А ДРЕС ШИНЫ MODBUS Адрес шины (двоичный, настраиваемая значимость от 1 до 247) DIP-переключатель [ A ] DIP 1 DIP 2 DIP 3 DIP 4 DIP 5 DIP 6...
  • Page 39: Индик Ация На Дисплее

    ® HYGRASGARD RFTM - LQ - CO - Modbus | Конфигурация ИНДИК АЦИЯ НА ДИСПЛЕЕ В стандартном исполнении на дисплее поочередно и циклично отображаются следующие измеренные значения с соответствующими единицами измерения: содержание углекислого газа (млн ), качество воздуха (VOC; %), температура (°C), относительная...
  • Page 40 ® HYGRASGARD RFTM - LQ - CO - Modbus | Конфигурация Таблица кодов ASCII для полей с точечной матрицей ASCII Символ ASCII Символ ASCII Символ ASCII Символ ASCII Символ Пробел “ & < > ü ä Ä ö Ö Ü °...
  • Page 41 ® HYGRASGARD RFTM - LQ - CO - Modbus | Телеграммы ТЕЛЕГРАММЫ Функция 04 — Чтение регистров ввода (Read Input Register) Регистр Параметр Тип данных Значение Диапазон 3x0001 Считывание 4 с Со знаком 16 бит 350...5000 350...5000 млн 3x0002 Фильтрация 32 с Со знаком 16 бит 350...5000 350...5000 млн...
  • Page 42 ® HYGRASGARD RFTM - LQ - CO - Modbus | Телеграммы Функция 05 — Запись значения одного флага (Write Single Coil) Регистр Параметр Тип данных Значение Диапазон 0x0001 Сброс (Autozero) CO2 Бит 0 0 / 1 OFF - ON 0x0002 Сброс (Autozero) VOC Бит...
  • Page 43 ® AERASGARD RFTM - LQ - CO - Modbus | Подключение Rev. 2017 - V14 RU intro Общая структура шины MODBUS RTU-Master Пассивное Активное ответвление ответвление RS-485 Оконечная Оконечная Магистральная нагрузка нагрузка линия шины шины (магистральный кабель) Тупиковая линия (ответвитель- Slave n ный...
  • Page 44: Монтаж И Подключение

    Монтаж и подключение Приборы следует устанавливать в обесточенном состоянии. Указания к механическому монтажу: Подключение должно осуществляться исключительно к безопасно Монтаж должен осуществляться с учетом соответствующих, малому напряжению. Повреждения приборов вследствие действительных для места измерения предписаний и стандартов несоблюдения упомянутых требований не подлежат устранению по (напр., предписаний...
  • Page 45 Указания к продуктам В качестве Общих Коммерческих Условий имеют силу исключительно наши Условия, а также действительные «Общие условия поставки продукции и услуг для электрической промышленности» (ZVEI) включая дополнительную статью «Расширенное сохранение прав собственности». Помимо этого, следует учитывать следующие положения: – Подключение прибора должно осуществляться исключительно к безопасно малому напряжению и в обесточенном состоянии. Во...
  • Page 47 Reprints, in part or in total, are only permitted with the approval of S+S Regeltechnik GmbH. La reproduction des textes même partielle est uniquement autorisée après accord de la société S+S Regeltechnik GmbH. Перепечатка, в том числе в сокращенном виде, разрешается лишь с согласия S+S Regeltechnik GmbH.
  • Page 48 D G F r Busadresse, binärcodiert Bus address, binary coded Adresse du bus, code binaire Адресс шины, двоичный 0 0 0 0 0 0 0 1 0 0 1 1 0 0 1 1 0 1 1 0 0 1 0 1 1 0 0 1 0 1 1 1 1 1 0 0 1 0 0 1 0 0 0 0 0 0 1 0...

Table des Matières