Installation

7.1 General Information

The following connections need to be established on the heat
pump:
Fresh and exhaust air
Flow and return flow of the heating system
Condensate outflow
Outflow for the pressure relief valve
Temperature sensor
Voltage supply

7.2 Air Connection

7.2.1 Air Connection General Information
CAUTION!
Do not restrict or block the area around the air intake or outlet.
The air intake opening of the device is solely designed for direct
connection to a wall opening. The wall opening can be provided
with air duct and sealing collar for this purpose. See the illustra-
tion in the appendix under Installation Dimensions.
The glass fibre reinforced concrete air ducts offered as acces-
sories are moisture-resistant and diffusion-free.
The sealing collar is used to seal the air ducts on the heat pump.
The air ducts are not screwed directly onto the heat pump. Only
the rubber seal comes into direct contact with the heat pump
when the system is installed correctly. This guarantees easy as-
sembly and disassembly of the heat pump and also ensures
that solid-borne sound is well insulated.
It must also be ensured that the interior side of the wall opening
is lined with thermal insulation to prevent the wall from becom-
ing cold and to prevent moisture from penetrating the wall. The
enclosed fixing accessories can be used for attachment to the
wall.
EN-6
The air outlet can be optionally mounted directly to a wall open-
ing or to a longer duct (available as an accessory). Use the same
mounting procedure as for the air inlet.
If a flange-mounted air duct is used on the air outlet side, it is
secured with 4 M8 x 16 hexagon bolts in the threaded holes
provided. When doing this, ensure that the air duct stubs only
touch the insulation. There should be no contact with the exter-
nal sheeting.
Observe the external and internal dimensions as specified in
the figure. Also ensure that the vibration and duct isolation are
adequate.
452161.66.20a · FD 0106
8 x 80
M 4 x 8
M 8 x 16
www.glendimplex.de
LIK 8TES