Start up
- Adjusting burner output
B
A
D
12
www.ecoflam-burners.com
1
2
VERSION P
E
T
A
L I
2
D
E
T
A
L I
1
Adjustment of gas solenoid valve
Refer to the gas train manual for
the gas setting of the gas train
selected.
Optimising combustion values
The factory setting shall be modified
according to the output requeired.
N.B. observe the minimum required
flue gas temperature specified by
the boiler manufacturer and the
WARNING
requirements demanded of ue gas ducts
for avoiding condensation.
Warning: Recording of initial
commissioning data is recom-
mended.
Regulating the combustion of the one-
stage burner
• position the air valve in the fully open set-
ting (pos. 4).
(for particularly low power only, if the re-
duction of air is not sufficient with the head
in position 1, reduce the opening of the air
valve).
• dose the air by moving the combustion
head (figure) to suit the power required (as
shown in figure).
• dose the gas by regulating the gas ramp
(see figure in the ramp manual).
Firing head setting (1).
To act on the screw in fi gure:
• turn Allen key till you reach the
requested value (index 1-5).
Risk of air blast!
Continuously check CO, CO 2 and
soot emissions when adjusting the
output of the burner. Optimise combustion
values in the event of CO formation. CO
must not exceed 50 ppm.
420010962200