Burner Installation; Hydraulic Circuit - Ecoflam MAIOR P 150.1 AB Mode D'emploi

Masquer les pouces Voir aussi pour MAIOR P 150.1 AB:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14
1
1
2
MAXIMUM LENGTH OF SUCTION LINES FOR TWO-PIPE SYSTEM
Two-pipe siphon feed system
Two-pipe lift system
To correct length of pipes is calculated by summing up the length of all vertical and horizontal right sections and bends. The static
suction head will be the distance between the non-return valve and the
burner's pump axle. The depression must not be greater than 0.45 bar; should it be higher, some damages could occur to the
pump, with consequent increase in mechanical noises and ,eventually, a failure.

BURNER INSTALLATION

2
3
1
4 5

HYDRAULIC CIRCUIT

4
5
1 -
HOSE
2 -
OIL FILTER
3
3 -
OIL COCK
4 -
SUCTION
5 -
RETURN
H
9
420010331900 Maior P 150.1/200.1 AB
6
7
1 - BURNER
2 - NUT
3 - WASHER
4 - GASKET
5 - BOLT
6 - BOILER
7 - GASKET
VS
V1
V2
Pipe length
H (m)
AJ 6
(m)
ø 14 mm ø 16 mm
0
22
38
0,5
25
45
1
30
50
2
35
60
3
38
70
3,5
40
80
Pipe length
H (m)
AJ 6
(m)
ø 14 mm ø 16 mm
0
25
45
0,5
20
38
H
1
18
33
2
10
20
3
5
10
3,5
2
4
J 7
(m)
ø 14 mm ø 16 mm
29
16
18
33
37
20
25
44
52
29
55
31
J 7
(m)
ø 14 mm ø 16 mm
16
29
26
14
12
22
7
14
7
3
1
4
EN

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Maior p 200.1 ab

Table des Matières