BLOWER
SPEED
0.2" (W.C.)
HIGH
1680
1210
MED-HIGH
MED-LOW
1110
960
LOW
LOCATION
FURNACE
SIDES
SUPPLY PLENUM WITHIN 6 FEET OF FURNACE
ACCESS PANEL TO BLOWER
BACK
FURNACE OR PLENUM
TOP
HORIZONTAL WARM AIR DUCT WITHIN 6 FEET OF FURNACE
FURNACE (COMBUSTIBLE FLOOR)
BOTTOM
AROUND FLUE PIPE
FLUE PIPE
FRONT
FURNACE
Table 9: Airflow data, models with 1/2 HP 4 speed motors
EXTERNAL STATIC PRESSURE WITH AIR FILTER
0.3" (W.C.)
0.4" (W.C.)
1640
1190
1070
940
Table 10: Minimum clearances from combustible material
APPLICATION
0.5" (W.C.)
1600
1590
1180
1160
1040
1010
920
890
CLEARANCES (combustible
materials)
2.54 cm (1")
2.54 cm (1")
10.16 cm (4")
5.08 cm (2")
5.08 cm (2")
0 cm (0")
22.86 cm (9")
20.32 cm (8")
15
0.6" (W.C.)
0.7" (W.C.)
1540
1460
1130
1110
970
930
860
830
RECOMMANDED
ACCESS FOR SERVICE
0.6 m (24")
0.6 m (24")
0.6 m (24")