8311

4.3 Electrical connection

Always ensure the power supply is switched off before working on the
device All the cable plugs must be plugged out Use:
- a shielded cable with an operating temperature > +80 °C
- a high quality voltage supply (filtered and regulated)
install the following security devices:
- for the power supply: 1a-fuse
- for the relay: a max. 3-a-fuse and a circuit breaker (depending
on the application).

4.3.1 Cable plugs

208 cable plug (supplied)
- To open the plug, unfasten screw [1]
- Remove part [3] from part [2]
- Unscrew cable gland [5]
- Insert cable into part [2] via cable gland
- Wire part [3] (see 433)
- Replace part [3] into part [2], by 90°-steps
- Tighten cable gland [5] Place gasket [4] between the cable plug and
the fixed connector of the controller and plug the 2508 onto the fixed
connector
- Tighten screw [1] to ensure tightness and correct electrical contact
1
2
4
3
1
5