6.6.5. Operation PROPORTIONAL/VAV mode
In this mode the control box is ready to work with one or two analog inputs (4-20mA or 0-10V). The control box works according
to the parameter of maximum demand. Sensors are connected to the analog inputs J5 and/or J6.
Once changed the operation mode to PROPORTIONAL/VAV, following parameters will appear:
SENSOR IN1
<
OFF
OK
OK
OK
IN1 RANGE
<
100%HR
OK
OK
OK
Press any key to return to main screen
Operation PROPORTIONAL/VAV mode
SENSOR IN1
< 0-10V%HR OK
SENSOR IN1
< 0-10VTempOK
SENSOR IN1
< 0-10VCO2 OK
Sensor IN1:
- NO SENSOR: No sensor connected to this input
- 0-10V/4-20mA %HR: Humidity sensor with output analog signal 0-10V/4-20mA
- 0-10V/4-20mA TEMP: Temperature sensor with output analog signal 0-10V/4-20mA
- 0-10V/4-20mA CO2: CO2 sensor with analog signal 0-10V/4-20mA
Press
or
to modify the scale of the external
sensor used
SENSOR IN1
< 4-20mA%HR OK
SENSOR IN1
< 4-20mATempOK
SENSOR IN1
< 4-20mACO2 OK