4.5 Non self locking models
Non self locking models allow the gate to move manually, without having to use a release key when the power fails. Non self locking
versions are equipped with a holding brake when opening/closing, This means the gate will be self locking in normal operation.
Refer to the attached sheet for the correct procedure of cleaning / maintenance of the electro-brake. DEA System reminds that the
operations must be performed by qualified personnel.
5.1 ELECTRICAL CONNECTIONS FOR 24V MODELS
Execute the wiring following the directions of "Table 1" and diagrams on page 23.
WARNING To ensure an appropriate level of electrical safety always keep the 230V power supply cables apart (minimum 4mm in the
open or 1 mm through insulation) from low voltage cables (motors power supply, controls, electric locks, aerial and auxiliary circuits
power supply), and fasten the latter with appropriate clamps near the terminal boards.
WARNING Connect to the power supply 230 V ~± 10% 50 Hz through a multi pole switch or a different device that can ensure multi pole
disconnection from the power supply, with a contact opening of 3 mm.
WARNING To connect the encoder to the control panel, use only a dedicated cable 3x0,22mm
1-2
+24 V
22 V ~ transformer power supply input
3-4
5-6
24 V
7-8
Operator 1 output
9
Connection of motors metallic parts
10-11
Operator 2 output (if present)
12-13
24 V
14 (-)
14-15
15 (+)
16-17
24 V
18 - N.C.
18-19
19 - Com
20 - N.C.
20-21
21 - Com
22 - N.C.
22-23
23 - Com
24 - N.C.
24-25
25 - Com
26 - N.O.
26-27
27 - Com
28 - N.O.
28-29
29 - Com
30
Aerial signal input
31
Ground aerial input
32 (+)
32-33
33 (-)
Encoder selection Jumper:
J5
J9
•A position = operators with encoder (remind to set P029=0)
•B position = operators without encoder (remind to set P029=1)
22
All manuals and user guides at all-guides.com
Table 1 "terminal board connections"
power supply output for auxiliary devices 200mA
battery power supply or photovoltaic accumulator Green Energy input (follow carefully polarity indications).
max 15 W output for open gate fix warning light (if P052=0), flashing (if P052=1) or courtesy light (if P052>1)
"Boost" output for electric-lock, max 1 x art. 110 (if P062=0), 24V pulse output, max 5W (if P062=1), step
by step (if P062=2), electro-brake output for not self-locking operators (if P062=3), output for electric-lock
power supply via external relay (if P062=4), output for electro-magnets power supply for barriers (ifP062=5)
or temporized output (if P062>5).
Flashing light output max 15W art. Lumy/24A/S
Input 6 FCC 1. If it intervenes it stops M1 closing. If unused, short circuit.
Input 5 FCA 1. If it intervenes it stops M1 opening. If unused, short circuit.
Input 4 PHOTO 1. When enabled (see parameter P050 in the table), activation of PHOTO
1 provokes: an inversion of direction (during closing), the arrest of the movement (during
opening), prevent the start (gate closed). If unused, short circuit.
Input 3 SAFETY. If activated, it causes the inversion. See P055 and P056 on the parame-
ters table. If unused, short circuit.
Input 2 PED. If activated, it opens motor nr. 1 only.
Input 1 START. In case of intervention it provokes: the operator opening or closing. It may
operate as "inversion" mode (P049=0) or "step by step" mode (P049=1).
DE@NET mains input (unused at the moment)
.