Hazardous Area
Zone 2 and 22
Terminal 1,2
Terminal 1,2
Ex nA & ec
Ex ic
Vmax= 37 VDC
Ui = 37 VDC
Li = 0 μH
Ci = 1.0 nF
Vmax= 30 VDC
Ui = 30 VDC
Li = 0 μH
Ci = 1.0 nF
Terminal 3,4,5,6,7,8,9
Ex nA & Ex ec
Vmax = 7.2VDC
General installation instructions
If the enclosure is made of non-metallic materials, or if it is made of metal having a
paint layer thicker than 0,2 mm (group IIC), or 2 mm (group IIB, IIA, I), or any thickness
(group III), electrostatic charges shall be avoided.
For an ambient temperature ≥ 60ºC, heat resistant cables shall be used with a rating of
at least 20 K above the ambient temperature.
The enclosure shall be suitable for the application and correctly installed
The distance between terminals, inclusive the wires bare part, shall be at least 3 mm
separated from any earthed metal.
'TEST' connection, may only be applied when the area is safe, or if supply / output
circuit and the applied current meter are intrinsically safe.
9
8
7
+
1
‐
6
2
5
5431A
4
5434A
5435A
3
5437A
Terminal 1,2
Ex ic
Ui = 48 VDC
Pi = 851 mW
Li = 0 μH
Ci = 1.0 nF
Terminal 3,4,5,6,7,8,9
Ex ic
Uo: 7.2 VDC
Io: 12.9 mA
Po: 23.3 mW
Lo: 200 mH
Co: 13.5μF
5437V103-FR
Unclassified Area
Power
Supply
or
Zone 2
barrier
Temperature Range
T4: -50 ≤ Ta ≤ 85ºC
T5: -50 ≤ Ta ≤ 70ºC
T6: -50 ≤ Ta ≤ 55ºC
T4: -50 ≤ Ta ≤ 85ºC
T5: -50 ≤ Ta ≤ 75ºC
T6: -50 ≤ Ta ≤ 60ºC
35