Basic values
Basic
Input type
accuracy
≤ ±0.3°C
RTD
≤ ±0.2 Ω
Lin.R
EMC immunity influence .....................................
Effect of supply voltage variation ................ ≤ 0,005% of span / VDC
Vibration....................................................... IEC 68-2-6 Test FC
Lloyd's specification no. 1........................... 4 g / 2...100 Hz
Max. wire size.............................................. 1 x 1.5 mm2
Humidity ...................................................... < 95% RH (non-cond.)
Dimensions .................................................. Ø 44 x 20.2 mm
Tightness (enclosure/terminal)..................... IP68 / IP00
Weight.......................................................... 50 g
Electrical specifications, input:
RTD
Min.
type
value
Pt100
-200°C
Ni100
-60°C
0 Ω
Lin.R
RTD and linear resistance input:
Max. offset................................................... 50% of selec. max. value
Cable resistance per wire (max.) ................. 10 Ω
Sensor current ............................................. > 0.2 mA, < 0.4 mA
Effect of sensor cable resistance
(3-wire) ......................................................... < 0.002 Ω/ Ω
Sensor error detection................................. Yes
Output:
Current output:
Signal range................................................. 4...20 mA
Min. signal range ......................................... 16 mA
Updating time .............................................. 135 ms
Load resistance ........................................... ≤ (Vsupply- 8) / 0.023 [Ω]
Load stability ............................................... < ±0.01% of span/100 Ω
16
Temperature
coefficient
≤ ±0.01°C / °C
≤ ±20 mΩ / °C
±0.5% of span
Max.
Min.
value
span
+850°C
25°C
+250°C
25°C
10000 Ω
30 Ω
Sensor error detection :
Programmable ............................................. 3.5...23 mA
NAMUR NE43 Upscale ............................... 23 mA
NAMUR NE43 Downscale ........................... 3.5 mA
Ex data:
U i ................................................................. 28 VDC
I i .................................................................. 120 mADC
P i .................................................................. 0.84 W
L i .................................................................. ≤ 10 µH
C i ................................................................. ≤ 1 nF
EEx approval CENELEC:
DEMKO 99 .................................................. ATEX 126964
ATEX ........................................................... 0539
Max. amb. temperature for T1...T4 ............. 85°C
Max. amb. temperature for T5 and T6 ....... 60°C
Applicable in zone ....................................... 0, 1 or 2
FM ............................................................... IS, CL. I, DIV. 1, GP. A-D
Entity, FM Control Drawing No. .................. 5300Q502
Observed authority requirements :
EMC 89/336/EEC, Emission ....................... EN 50 081-1, EN 50 081-2
Immunity ...................... EN 50 082-2, EN 50 082-1
ATEX 94/9/EC .............................................. EN 50 014 and EN 50 020
FM Class Number ....................................... 3600, 3610
Of span = Of the presently selected range
II 1 G
EEx ia IIC T1...T6
Standard:
17