13.3
Specification
Table 13.3: General Specification
Operating Temperature
Storage Temperature
Humidity
Vibration Resistance - DIN Rail mounting
Shock Resistance
Noise Immunity
Dielectric Withstand Voltage
Insulation Resistance
Operation Ambience
Table 13.4: Power Specification
Power Supply
Maximum Power Consumption
Table 13.5: Adjustment Standard
EC Directive
Table 13.6: Hardware Specifications
Item
Input
Specification
Compensated
Range
Overall accuracy
Resolution
D/A Conversion
Time
Isolation Circuit
Item
Item
Item
Certification of UL/cUL
Centigrade (°C)
Thermocouple K Type, JIS 1602-1995 (IEC 584-1 1977, IEC 584-2 1982),
-50°C - 450°C
±2.0% (range of all temperatures) and
±1.5% (at 25°C)
No isolation between channels (input/output) and power
35 ~ 85% Relative humidity, no condensation
Conforms to IEC 68-2-6; 10-57: Hz: 0.075mm
57-150Hz:9.8m/s
X, Y, and Z: 10 times (80 minutes in each direction)
Conforms to IEC 68-2-27: 147m/s
Time: 11ms 3 times in each direction X, Y and Z
1000 Vpp, 1µs, 30-100Hz tested by a noise simulator
500V AC~>1min per EN60730-1 between all terminals
and the DIN43880 control box or equivalent.
7MΩ 500V DC EN60730-1 between all terminals and
the DIN43880 distribution box or equivalent
EMC
Specification
Isolated Type.
20.5ms
Content
(-25) - 55°C / (-13) - 131°F
(-30) - 70°C / (-22) - 158°F
Constant Amplitude
2
Acceleration. Sweep Count for
2
To be free of corrosive gases
Content
24V DC +20%, -15%
0.5W
Content
EN61131-2: 2007
EN60730-1: 2011
File number: E95239
Fahrenheit (°F)
-58°F - 842°F
±2.0% (range of all temperatures) and
±1.5% (at 77°F)
1°C
AL2-2TC-ADP 13
Acceleration, Action
ENG-74