Commissioning
Enabling the standard device via the communication module
Enabling ECSXX via the communication module
Step
Procedure
1.
Select "AIF" control
interface via code.
2.
Set C0142 = 0
3.
Set terminals X6/SI1
and X6/SI2 to HIGH
level
4.
The controller now accepts parameter and process data.
72
Comments
See documentation for the corresponding ECS controller.
Example of the first commissioning with signal configuration
"1013":
Write (C0005 = 1013)
l
Class: 0x6E (110
dec
l
Instance: 0x5
l
Attribute: 1
l
Service code: Set Single Attribute
l
Data send: 0x9A9250 (10130000
See "Protection against uncontrolled restart" (^ 73).
Terminals X6/SI1 (controller enable/inhibit) and X6/SI2 (pulse
enable/inhibit) are always active and have to be on HIGH level
during DeviceNet operation. Otherwise the controller cannot be
enabled via DeviceNet.
l
)
)
dec
EDKMF2179 DE/EN/FR 4.1