Les langues disponibles

Bus cable length
Depending on the baud rate and the cable type used (thick cable/thin cable), the following
bus cable lengths are possible:
Baud rate [kbps]
125
250
500
If both thick and thin cable types are used, the maximum cable lengths can be defined
according to the baud rates as follows:
Baud rate [kbps]
125
250
500
L
: thick cable length
thick
L
: thin cable length
thin
)
Note!
Select a baud rate in dependency of the data volume, cycle time and number
of nodes just high enough to suit your application.
EDKMF2179 DE/EN/FR 4.1
Thick cable
500
250
100
Max. bus cable length
500 m = L
+ 5 L
thick
thin
250 m = L
+ 2.5 L
thick
thin
100 m = L
+ L
thick
thin
l
Electrical installation
Bus cable length
Bus cable lengths [m]
Thin cable
100
6
61