9.4 SUPERVISOR PARAMETERS
MODBUS BASED (0)
DIGITAL VARIABLES (READ COILS)
BMS
Description
Address
1
Supervisor ON/OFF State
2
Air Pressure Switch 1
3
Air Pressure Switch 2
4
B1ProbeAlarm
5
B2ProbeAlarm
6
B3ProbeAlarm
7
B4ProbeAlarm
8
B5ProbeAlarm
9
B6ProbeAlarm
10
B7ProbeAlarm
11
B8ProbeAlarm
12
High Pressure Switch Alarm
13
High Temperature Safety Switch Alarm
14
HighADInletTemp Warning
15
LowADInletTemp Alarm
16
HighElHeaterTemp_1 Alarm
17
HighElHeaterTemp_2 Warning
18
LowElHeaterTemp_1 Warning
19
LowElHeaterTemp_2 Warning
20
HighPurgeAirTemp Warning
21
HighDewPTemp Warning
22
HighDischCompTemp Alarm
23
LowPressColumn1 Warning
24
HighPressColumn1 Warning
25
LowPressColumn2 Warning
26
HighPressColumn2 Warning
27
MancatoRaffreddamento Warning
28
CompressorProtection Warning
29
LowEvapTemp Alarm
30
AuxEvapTemp Alarm
31
LowPressureSwitch Alarm
32
HeaterThermostat Alarm
33
Filters Warning
34
Allarm Clock
35
Drain Warning
36
FridgeSwitchAlarm
PointMeterPresent
37
(in Summer)
38
AbilitaSummerMode
39
SummerMode
40
PresenzaAcqua_LivCap
41
HeaterTermostatoSicurezza
42
RemoteONOFFState
44
Digital Input
45
Digital Input
46
Digital Input
47
Digital Input
Default "Read/
Variable name
Write"
0
R/W
SupervisorONOFFState
0
R
AirPressureSwitchA
0
R
AirPressureSwitchB
0
R
B1ProbeAlarm
0
R
B2ProbeAlarm
0
R
B3ProbeAlarm
0
R
B4ProbeAlarm
0
R
B5ProbeAlarm
0
R
B6ProbeAlarm
0
R
B7ProbeAlarm
0
R
B8ProbeAlarm
0
R
AL_HighPressureSwitch
0
R
AL_HTSafetySwitch
0
R
W_HighADInletTemp
0
R
Al_LowADInletTemp
0
R
W_HighElHeaterTemp_A
0
R
W_HighElHeaterTemp_B
0
R
W_LowElHeaterTemp_A
0
R
W_LowElHeaterTemp_B
0
R
W_HighPurgeAirTemp
0
R
W_HighDewPTemp
0
R
Al_HighDischCompTemp
0
R
W_LowPressColumn1
0
R
W_HighPressColumn1
0
R
W_LowPressColumn2
0
R
W_HighPressColumn2
0
R
W_MancatoRaffreddamento
0
R
Al_CompressorProtection
0
R
Al_LowEvapTemp
0
R
Al_AuxEvapTemp
0
R
Al_LowPressureSwitch
0
R
AL_HeaterThermostat
0
R
W_Filters
0
R
AllarmeClock
0
R
W_Drain
0
R
FridgeSwitchAlarm
0
R/W
DewPointMeterPresent
0
R/W
AbilitaSummerMode
0
R/W
SummerMode
0
R
PresenzaAcqua_LivCap
0
R
HeaterTermostatoSicurezza
0
R
RemoteONOFFState
0
R
AirCOmpressorONOFF
0
R
HPSwitchState
0
R
HTSafetySwitchState
0
R
LPSwitchState
ATT140-340
48
Digital output
49
Digital output
50
Digital output
51
Digital output
52
Digital output
53
Digital output
54
Digital output
55
Digital output
56
Global (general) alarm(Digital Output)
57
Digital output
58
Digital output
61
Digital output (machine Status)
64
Remote ON/OFF
99
Mode Compressor (normal/Cycling)
1
R
DOut_HeaterContactor
1
R
DOut_Compressor
1
R
DOut_ValvolaBypass
1
R
DOut_MoistureDrain
1
R
DOut_ADEVInColumnA
1
R
DOut_ADEVInColumnB
1
R
DOut_EVPurgeA
1
R
DOut_EVPurgeB
0
R
GLOBAL_ALARM
1
R
DOut_PressDischargeA
1
R
DOut_PressDischargeB
1
R
DOut_StatoMacchina
0
R/W
ParRemoteONOFFMode
1
R/W
ModoCompressoreCycling
12