Consignes de sécurité pour les installations homologuées U
6.1.6
Consignes de sécurité pour les installations homologuées U
J
Warnings !
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
EDS84ABD302 FR 4.0
The device has no overspeed protection.
The integral solid state protection does not provide branch circuit protection
and that branch circuit protection has to be provided externally in
accordance with manufacturers instructions, the National Electrical Code
and any additional codes.
Suitable for use on a circuit capable of delivering not more than 200,000 rms
symmetrical amperes, at the maximum voltage rating marked on the
device.
Motor overload is provided at 125% of rated current. The overload trip point
must be enabled and adjusted by parameterization.
Shall be installed in a pollution degree 2 macro−environment.
Maximum surrounding air temperature: 55 °C (¶ 4.2)
Use minimum 75 °C copper wire only, except for control circuits.
l
Installation électrique
Remarques importantes
ou U
L
ou U
L
R
6
R
55