7.3.5
FM Approvals
TZIDC-120 Positioner, Model V18347-a042b2cd0e
IS/I,II,III/1/ABCDEFG/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C-901265 Entity, FISCO
Terminals
+11 / -12
+11 / -12
+11 / -12
+51 / -52
+41 / -42
+85 / -86
NNI/I/2/ABCD/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
S/II,III/2/EFG//T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
Enclosure type 4x
a = Case/mounting – 1, 2, 5 or 6
b = Output/safe protection – 1, 2, 4 or 5
c = Option modules (shutdown) – 0 or 4
d = Optional mechanical kit for digital position feedback – 0, 1 or 3
e = Design (varnish/coding) – 1 or E
Equipment Ratings:
TZIDC-120 Positioners
Intrinsically safe, Entity and FISCO, for Class I, II and III, Division 1,
Applicable Groups A, B, C, D, E, F, G; nonincendive for Class I, Division 2,
Group E, F and G hazardous (classified) indoor and outdoor NEMA 4x locations.
The following temperature code ratings were assigned for the equipment and protection
methods described above:
T6 in ambient temperatures of 40 °C
T5 in ambient temperatures of 55 °C
T4 in ambient temperatures of 85 °C
CI/TZIDC/110/120-FR
Entity and FISCO Parameters
Type
Groups
Entity
A-G
FISCO
A-G
FISCO
C-G
Entity
A-G
Entity
A-G
Entity
A-G
TZIDC, TZIDC-110, TZIDC-120
Caractéristiques techniques Ex importantes
Parameters
Vmax
Imax
24 V
250 mA
17,5 V
360 mA
17,5 V
380 mA
16 V
20 mA
16 V
20 mA
30 V
-
Pi
Ci
1,2 W
2,8 nF
2,52 W
2,8 nF
5,32 W
2,8 nF
-
60 nF
100 uH
-
60 nF
100 uH
-
3,7 nF
Li
7,2 uH
7,2 uH
7,2 uH
< 1 uH
65