Télécharger Imprimer la page

SMA SUNNY TRIPOWER STORAGE 60 Instructions D'installation page 42

Masquer les pouces Voir aussi pour SUNNY TRIPOWER STORAGE 60:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 135
9 Service
Internal Events
ID
Display
201-208 Internal
temperature
too high
209,
Voltage on
210
DC bus is
too high
211
Fan speed
too low
213-215 Contactor
failed to
close
216-218 Grid
measured
current high
219-221 Contactor/
relay failed
to close
225-240 Failure in
memory
241-245 Internal
communicat
ion failure
248
System-fault Internal CPU error.
249
Communica
tion
252-254 Grid current
too high
263
Internal
software
error
275
Internal
memory
failure
279
Temperatur
e sensor
error
42
STPS60-IA-xx-13
Description
The internal temperature of the
inverter is too high.
Voltage in DC link is too high.
Fan speed is too low.
Internal error. Voltage
measured before and after the
relay differs too much.
Current measured on AC side
is too high.
Internal error. Voltage
measured before and after the
relay differs too much.
Failure in memory/EEPROM.
Internal communications fault.
Communication error.
Current measured on AC side
is too high.
Internal error.
Failure in memory/EEPROM.
Temperature sensor error.
Measure
Verify that no objects or dust are on
top of the inverter and make sure
that the air ducts are clear and not
blocked.
If the event persists, reset the
inverter by disconnecting DC and
AC. If the event is repeated, check
the maximum DC voltage using the
display to see if it is above the limits.
Check whether the inverter fan is
blocked.
Contact the Service.
Contact the Service.
Contact the Service.
Restart the inverter. If the event
persists, contact Service.
Restart the inverter. If the event
persists, contact Service.
Restart the inverter. If the event
persists, contact Service.
Restart the inverter. If the event
persists, contact Service.
If the event repeats, contact Service. -
Restart the inverter. If the event
persists, contact Service.
Restart the inverter. If the event
persists, contact Service.
If the event persists, contact Service. -
SMA Solar Technology AG
DN
SMA Se
DC
O
rvice Lin
e
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
x
-
-
x
-
-
x
-
x
-
Installation Manual

Publicité

loading