5 Installation
Figure 8: Mount on non-flammable surface
Figure 9: Mount upright on vertical surface. A backward tilt of ten
degrees is allowed.
Figure 10: Avoid dust and ammonia gases
INFORMATION
When selecting the installation site, ensure that the
product and warning messages on the inverter are
visible at all times. For details, refer to Section
11, page 46.
INFORMATION
All ambient installation conditions must be met
(see Section 11.3, page 48).
INFORMATION
The safety clearances to other objects must be
maintained to ensure sufficient air circulation
(see Section 5.3, page 25).
24
STPS60-IA-xx-13
Observe clearances:
• When installing one or several inverters, observe the
safety clearances to ensure sufficient airflow.
Clearances are specified in figure 2.8 and on the wall
mounting bracket label.
• When installing several inverters, mounting them side
by side in a single row is recommended. Contact the
supplier for guidelines when mounting inverters in more
than one row.
• Ensure adequate clearance at the front, for safe
installation and service access to the inverter.