3.2
Further information on various parameters
P
1: B
ARAMETER
OILER TEMPERATURE
To display the boiler water outlet temperature.
P
2: F
ARAMETER
LOW TEMPERATURE
Used to display the boiler water outlet temperature on the valve
circuit.
P
3: H
ARAMETER
EATING CURVE OF THE CIRCUIT
"Boiler" heat curve
Maximum boiler temperature
Factory setting: 75 °C
Minimum boiler temperature in comfort mode
Factory setting: 30 °C
X Outside temperature (°C)
Y Water flow temperature (°C)
The factory setting of the heating curve is 1.5
P
4: G
ARAMETER
RADIENT OF VALVE CIRCUIT
Curve of heating circuit valve B
Maximum start temperature after valve
Factory setting: 50 °C
Maximum outlet temperature after valve
Factory setting: 20 °C
X Outside temperature (°C)
Y Valve start temperature (°C)
The slope of the circuit valve * 1 is regulated of factory with * 2.
8
B
A
B
4,0
,0
2,25
2,0
P
5: M
ARAMETER
AXIMUM TEMPERATURE OF HEATING CIRCUIT
The flow temperature for the heating circuit can be limited.
If the maximum temperature is modified, also modify if
necessary the boiler thermostat stop that limits the maximum
boiler temperature at 75 °C. To do so, take out the thermostat
button by pulling it up and moving the stop to the required
temperature limit hole with a pair of pliers.
For a standard installation without outside sensor, we
recommend to set the maximum temperature of the heating
circuit to a value less than or equal to 75 °C.
P
6: M
ARAMETER
AXIMUM OUTLET TEMPERATURE AFTER VALVE
For circuit B, this setting limits the outlet temperature on the
corresponding circuit.
If using underfloor heating, it is imperative to keep the
factory setting of the maximum outlet temperature after the
mixing valve at 50 °C.
The regulations also impose an independent safety device
which must cut off the supply of heat to the underfloor heating
circuit when the maximum temperature of the liquid reaches
65°C.
To meet this requirement, a safety thermostat must be
electrically connected to the TS contact on the pump connector.
P
7:
ARAMETER
A
UTOMATIC ADAPTATION AND ALLOCATION OF THE ROOM SENSOR
- Enabled (setting 1): automatic setting of the heating curve is
enabled.
- Blocked (setting 0): the heating curve is fixed. It can only be
modified manually.
- Room temperature sensor for circuit A: setting A
- Room temperature sensor for circuit B: setting B
P
8: I
ARAMETER
NFLUENCE OF THE ROOM SENSOR
Allows to adjust the influence of the ambient sensor on boiler water
the temperature or departure circuit valve.
0: the room sensor is ignored (for example : badly positioned remote
control)
1: low influence
3: average influence (recommended)
10: operating like room thermostat