1 Calibration
1
2
0
2
4
6
MODE
PROG
PROG
2 Total reset
To carry out a total reset (rebootstrapping of all the parameters), to
press simultaneously on the 3 following keys:
+ MODE +
3 Setting the RS 100 regulator parameters
The settings below have different functions and configure
the installation. They may only be changed by a qualified
professionnal.
The different parameters and settings are saved even after a
current cut off.
The various adjustable settings are given in the order in which they
appear in the "Fitter settings table" below.
To accede to the settings, press the clock
Programme
keys for 5 seconds. These are located under the
cover.
The data are stored after 2 minutes or when you press the MODE
key.
6
3
4
5
6
7
+
10
12
14
16
1
20
22
24
C
-
TANDARD
and Heating
"Installer" settings
Measure with a thermometer the room temperature in the room
where the regulator is installed.
Press key
Match the display with the reading on the thermometer using the +
and - keys.
Press keys
Using keys + and -, to regulate the correction of the clock which is
expressed in minutes per month (example: if the hour advances 3
minutes every 2 months, to regulate -1.5).
A=Access to the level fitter by simultaneous support during 5
seconds
RS 100
Room sensor calibration
and
simultaneously for 5 seconds.
Clock calibration
and
simultaneously.
19/07/07 - 300010276-001-A