SPE C IF I CAT I ON S
Installation Requirements
IMPORTANT NOTE:
When installing against a combustible
surface, a minimum 10"
(254)
fuel range with charbroiler or griddle and all 48" and 60"
models. Follow all minimum clearances to combustible
surfaces shown in the illustration on page 6.
|
4
Wolf Customer Care 800.222.7820
riser is required for a 36" dual
Electrical Requirements
Installation must comply with all applicable electrical codes.
Locate the electrical supply flush with the wall or floor
and within the shaded area shown in the illustration on
page 6. A separate circuit servicing only this appliance is
required.
If a power supply cord is used, the cord must be designated
for use with ranges and rated for 240 V, 30 or 50 amps
(refer to the chart below), and must include 3 or 4 conduc-
tors. A 4-conductor cord is required for installations where
grounding through the neutral is prohibited.
Performance may be compromised if the electrical supply is
less than 240 volts.
E L E C T R I C AL R E Q U I R E M E N T S — S I N G L E O V E N
Electrical Supply
Service
Total Amps
Max Connected Load
Min Supply Wire
E L E C T R I C AL R E Q U I R E M E N T S — D O U B L E OV E N
Electrical Supply
Service
Total Amps
Max Connected Load
Min Supply Wire
grounded, 240/208 VAC, 60 Hz
30 amp dedicated circuit
5.2 kW
L1, L2, ground—12 AWG
neutral—16 AWG
grounded, 240/208 VAC, 60 Hz
50 amp dedicated circuit
42.5
10.2 kW
L1, L2—8 AWG, ground—10 AWG
neutral—12 AWG
21