Installation
4

Information regarding UL

4.14
Information regarding UL
4.14.1

Field Wiring Power Terminals

MDP90A-...-
0100 (size 1)
0100 (size 1A)
0250
MDA90A-...-
0020 – 0120
0160 – 0240
0320 – 0480
MDD90A-...-
0020 – 0040
0020 – 0080
4.14.2

Short Circuit Current Rating

4.14.3

Branch Circuit Protection

Power supply
module
0100 (size 1)
154
Notice d'exploitation – MOVIDRIVE
Use 60/75 °C solid or stranded copper wire only sized at 14 AWG minimum. Sui-
table for 1 wire per terminal.
For double-axis modules use wire size 12 - 14 AWG
Tighten terminals to in-lbs (Nm) as follows
Line connection
X1
4.4254 – 5.3105 (0.5 – 0.6)
X1
4.4254 – 5.3105 (0.5 – 0.6)
X1
23.552 – 35.403 (3.0 – 4.0)
Motor connection
X2
4.4254 – 5.3105 (0.5 – 0.6)
X2
13.276 – 15.046 (1.5 – 1.7)
X2
23.552 – 35.403 (3.0 – 4.0
Motor connection
X2
4.4254 – 5.3105 (0.5 – 0.6)
X2
13.276 – 15.046 (1.5 – 1.7)
DC link connection
X4
23.552 – 35.403 (3.0 – 4.0
Suitable for use on a circuit capable of delivering not more than
5000 rms symmetrical amperes when protected by fuses and circuit breakers as
described in the tables below.
Max. voltage is limited to 500 V.
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
SCCR: 5 kA/ 500 V
when protected by:
Non semiconductor fuses (currents are
maximum values)
20 A / 600 V
®
modular
Tightening torque in-lbs (Nm)
Power supply module
Braking resistor terminals
X3
X3
X3
Single-axis module
-
-
-
Double-axis module
-
-
All modules
Inverse-time circuit breaker (currents
4.4254 – 5.3105 (0.5 – 0.6)
4.4254 – 5.3105 (0.5 – 0.6)
23.552 – 35.403 (3.0 – 4.0)
-
-
-
-
-
-
-
PE connection
23.552 – 35.403 (3.0 – 4.0
SCCR: 5 kA/ 500 V
when protected by:
are maximum values)
20 A / 500 V min.