4.4 Troubleshooting
Diagnostics
In case of operation faults or problems, the display flashes and the fault identification
code appears.
There are faults that cause permanent shutdown (marked with the letter "A"): to restore
operation just press the reset button (detail 6 -fig. 1) for 1 second or RESET on the op-
tional remote timer control if installed; if the boiler fails to start, it is necessary to firstly
eliminate the fault.
Faults marked with the letter "F" cause temporary shutdowns that are automatically reset
as soon as the value returns within the boiler's normal working range.
Table of faults
Table. 8 - List of faults
Fault
Fault
Possible cause
code
No gas
Ignition/detection electrode fault
A01
No burner ignition
Faulty gas valve
Insufficient gas supply pressure
Trap blocked
Electrode fault
Flame present signal with
A02
burner off
Card fault
Heating sensor damaged
Overtemperature protection
A03
activation
No water circulation in the system
Air in the system
Fume extraction duct safety
Fault F07 generated 3 times in the
A04
device activation
last 24 hours
Fault F15 generated for 1 hour (con-
A05
Fan protection activated
secutive)
Ionisation electrode fault
Flame unstable
Gas valve Offset fault
No flame after ignition stage
A06
(6 times in 4 minutes)
air/fume ducts obstructed
Trap blocked
The fume probe detects an exces-
F07
High fume temperature
sive temperature
Sensor damaged
F10
Delivery sensor 1 fault
Wiring shorted
Wiring disconnected
Sensor damaged
F11
Return sensor fault
Wiring shorted
Wiring disconnected
Sensor damaged
F12
DHW sensor fault
Wiring shorted
Wiring disconnected
Probe damaged
F13
Fume probe fault
Wiring shorted
Wiring disconnected
Sensor damaged
F14
Delivery sensor 2 fault
Wiring shorted
Wiring disconnected
No 230V power supply
F15
Fan fault
Tachometric signal interrupted
Fan damaged
F34
Supply voltage under 170V Electric mains trouble
F35
Faulty mains frequency
Electric mains trouble
Pressure too low
Incorrect system water
F37
Water pressure switch damaged or
pressure
not connected
Probe damaged or wiring shorted
F39
External probe fault
Probe disconnected after activating
the sliding temperature
A41
Heating sensor detached from
Sensor positioning
A44
pipe
A42
Heating sensor fault
Sensor damaged
No system H
Exchanger protection
F43
activation.
Air in the system
F52
Heating sensor fault
Sensor damaged
A61
Controller ABM03 fault
Controller ABM03 internal error
Cure
Check the regular gas flow to the
boiler and that the air has been
eliminated from the pipes
Check the wiring of the electrode and
that it is correctly positioned and free
of any deposits
Check the gas valve and replace it if
necessary
Check the gas supply pressure
Check the trap and clean it if
necessary
Check the ionisation electrode wiring
Check the card
Check the correct positioning and
operation of the heating sensor
Check the circulating pump
Vent the system
See fault F07
See fault F15
Check the position of the ionisation
electrode and replace it if necessary
Check the burner
Check the Offset adjustment at
minimum power
Remove the obstruction from the flue,
fume extraction ducts and air inlet and
terminals
Check the trap and clean it if
necessary
Check the exchanger
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the
fume probe
Check the wiring or replace the sensor
Check the 8-pin connector wiring
Check the 8-pin connector wiring
Check the fan
Check the electrical system
Check the electrical system
Fill the system
Check the sensor
Check the wiring or replace the sensor
Reconnect the external probe or
disable the sliding temperature
Check the correct positioning and
operation of the heating sensor
Replace the sensor
O circulation
Check the circulating pump
2
Vent the system
Replace the sensor
Check the earth connection and
replace the controller if necessary.
cod. 3541F562 - Rev. 02 - 09/2016
Fault
Fault
Possible cause
code
Controller not connected
No communication between
A62
controller and gas valve
Valve damaged
A63
F64
Controller ABM03 fault
Controller ABM03 internal error
A65
F66
A23
A24
F20
F21
Card parameter fault
Wrong card parameter setting
A26
F40
F47
5. TECHNICAL DATA AND CHARACTERISTICS
196
350
81
340
278
194
42
95
10
8
44
fig. 26 - General view
Table. 9 - Key of figures cap. 5
7 Gas inlet
8 Domestic hot water outlet
9 Cold water inlet
10 System delivery
11 System return
14 Safety valve
16 Fan
32 Heating circulating pump
36 Automatic air vent
37 Cold water inlet filter
39 Flow regulator
42 DHW temperature probe
44 Gas valve
56 Expansion tank
72 Room thermostat (not supplied)
74 System filling cock
81 Ionisation/ignition electrode
Cure
Connect the controller to the gas valve
Replace the valve
Check the earth connection and
replace the controller if necessary.
Check the card parameter and modify
it if necessary.
7
9
74
11
39
136
37
95 Diverter valve
104 Fuse
114 Water pressure switch
136 Flow meter
138 External probe (optional)
139 Remote timer control (optional)
154 Condensate drain pipe
186 Return sensor
191 Fume temperature sensor
193 Trap
194 DHW exchanger
196 Condensate tray
241 Automatic bypass
256
278 Double sensor (Safety + Heating)
340 Bypass pipe
350 Fan/Burner assembly
A ON/OFF switch (configurable)
EN
191
56
186
193
14
36
114
32
41