Layout Diagram With Vaporisation; Operating Anomaly - baltur BTG 3 Notice D'instructions

Masquer les pouces Voir aussi pour BTG 3:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LAYOUT DIAGRAM WITH VAPORISATION

eventual emergency gas phase connection
tank
Warnings
The vaporizer is considered a dangerous point and should
therefore be situated at a safe distance from any building.
The electrical system must be AD-EP (anti-deflagration-
explosion proof).
The L.P.G. pipelines must be made of SS steel with welded
or flanged joints NP 40 (nominal pressure 40 bar). Threaded
joints are prohibited.

OPERATING ANOMALY

tYpe of IrregULarItY
The burner does not start.
The burner starts but the flame
does not ignite. The burner stops
consequently.
The burner starts and the flame
ignites then the burnes stops.
proBaBLe CaUSe
Lack of currente.
Gas does not reach the burner.
The gas valves do not open.
There is no spark at the
electrode.
The air pressure switch does
not give it's consent to the
control box
The control electrode does
not detect or detects the flame
improperly.
20 / 22
0006080742_201306
1st stage reducer unit
vaporizer
/ Specific materials /
1)
Liquid recovery valve.
2)
Liquid delivery cock with flow limiter.
3)
Steel fitting with welded tang and copper washer.
4)
18 bar safety valve with welded steel fitting.
rImeDY
Check the fuses of the feed line. Check the fuses of the
control box. Check the line of the thermostats and the gas
pressure switch.
Check the opening of the detecting devices located along
the feeding pipes.
Check the valves operation.
Check the operation of the ignition transformer. Check the
position of the electrodes ends.
Check the setting and operation of the air pressure switch.
Check the position of the control electrode. Check the valve
of the ionisation current.

Publicité

Table des Matières
loading

Table des Matières