After lockout. the red fault signa llamp will remaln steady on. In thal conditio visual diagnostics of the cause of fault acccording to the error
code table can be activated by presslng the lockout reset button for more than 3 seconds. Pressing the reset button again for at least 3
seconds, interface diagnostics will be activated
The followlng sequence activates the diagnostics of Ihe cause of fault:
red blink code of signal lamp (LeD)
2 blinks
ll
3 x blinks
lll
4 blinks
llll
5 blinks
lllll
6 blinks
llllll
7 blinks
lllllll
8 x blinks
llllllll
9 blinks
lllllllll
10 blinks
llllllllll
During the time the cause of fault is diagnosed, the control outputs are deactivated
- Burner remains shut down
- External fault indication remains deactivated
- Fault status signal «AL» at terminal 10, according to the error code table
The diagnostics of the cause of fault is quit and the burner switched on again by resetting the burner
control. Press thelockout reset button for about 1 second (< 3 seconds).
error code table
«aL» at term. 10
possible cause
No establishment of flame at the end of «TSA» -Faulty or soiled fuel
valves -Faulty or soiled flame detector -Poor adjustment of burner, no
On
fuel -Faulty ignition equipment
«LP» faulty -No or faulty air pressure signal after completion «t10» -
On
«LP» is welded in normal position
Extraneous light when burner startup
On
On
Time out «LP» - «LP» is welded in working position
On
Free
Too many losses of flame during operation (limitation of repetitions)
-Faulty or soiled fuel valves
On
-Faulty or soiled flame detector
-Poor adjustment of burner
On
Free
On
Free
Off
Wiring error or internal error, output contacts, other faults