Modification.of.the.pre-Setting; Setup.and.bus.system.control - FAAC 624 BLD Mode D'emploi

Masquer les pouces Voir aussi pour 624 BLD:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 40
Example of sequence of states displayed starting from barrier
closed:
00
Closed
03
Open
04
Pause (if present)
0 1
In the sequence, states
correspond to pre-flashing at opening and at closing,
respectively.

5.2.. MODIFICATION.OF.THE.PRE-SETTING.

The modification of the
automatically load 6 different configurations modifying all
programming values at every level with preset values.
This possibility is a convenient starting point for subsequent
rapid 'fine tuning' of the 64 BLD for functioning with 6
different types of installation.
6 PRE-SETTINGS may be selected:
0 1
Default FAAC for barriers
02
Default RESERVED FOR FAAC
03
Default for the FAAC CITY 75 H600 and H800 range
04
Default for FAAC CITY 75 H700 K
05
Default for J75
06
Default for J75K
To implement loading of the values of one of the 6
pre-settings, select the required pre-setting
04
05
06
and exit 1st level programming.
,
,
)
0 1
EXAMPLE: selecting
and exiting st level programming, all
the FAAC default values which can be found in the st, nd
and rd level tables in the "Default" column are loaded. The
64 BLD is therefore configured for movement of a barrier.
. THE.LOADING.OF.A.PRE-SETTING.CANCELS.ALL.
THE.MODIFICATIONS.PREVIOUSLY.MADE.AT.ANY.
PROGRAMMING.STEP ..IF.YOU.DO.NOT.WISH.TO.
LOAD.ANY.. PRE-SETTING,.LEAVE.THE..
00
AT.
.
dF
The
step, unlike the others, does not store
,
the value selected but returns to show
again, as standard condition.
It is therefore not possible to identify what pre-setting was
previously set.
If you do not wish to load any pre-setting, ALWAYS leave
dF
00
the
step at value
and move on to the following
programming step.
Ensure. that. you. load. the. desired. default. and.
exit. 1st. level. programming. BEFORE. modifying.
other. steps,. in. order. to. avoid. deleting. all. the.
modifications.made.
To learn more about the specifications of each pre-setting,
refer to chapter 0 on page 5.
02
Opening
06
Closing
05
and
are not shown; these
dF
parameter enables you to
0 1
02
(
,
dF
.STEP.

5.3.. SETUP.and.BUS.SYSTEM.CONTROL

Each time you install one or more BUS accessories (as
explained in chapter 4.) these must be stored on the
board.
Storage is performed as follows:
- enter the first programming level as explained in chapter.
5.;
bu
- at the
programming step, release programming
push-button F and press push-button + for  second.
The display shows
the standard condition indicated in fig. 0. The storage
procedure is finished.
bu
The
programming step also has the function of displaying
the status of the BUS technology accessories. Figure 9
indicates the exact correspondence between the segments
of the display and the inputs.
Segment ON = closed contact
Segment OFF = open contact
The configuration for correct operation of
the automated system should show the three
horizontal segments ON as in figure 10.
In case of engagement of the closure photocells,
the upper and lower segments switch off, leaving
the central segment on, as in figure .
In case of engagement of the PULSE GENERATOR
03
OPEN pair, the corresponding vertical segment
,
,
switches on for the engagement time of the pair,
as illustrated in figure .
The PULSE GENERATOR OPEN pair of photocells, if engaged,
commands opening of the application and prevents its
closure until it is released.
If no pair of BUS photocells is present on the
system, the
show the display in figure 10.
The BUS communication system uses a self-diagnostic function
00
able to supply reports of incorrect connection or of erroneous
configuration of the BUS accessories.
The display shows the
when a SHORT-CIRCUIT is present along
the BUS line, as in figure . Check the
connections made (chapter.4.).
The display shows the
FLASHING, as in figure 4, if more than
one pair of photocells should have the
same address.
In this latter case, check all the addresses set on all the
photocells installed, referring to chapter 4..
8
--
for an instant and then returns to
FSW CL = BUS photocells
closing
OPEN = BUS photocell
pulse generators OPEN
Fig. 10
Fig. 11
Fig. 12
bu
programming step will still
cc
signal FLASHING
Fig. 13
Er
message
Fig. 14
Fig. 9

Publicité

Table des Matières
loading

Table des Matières