LipuSmart-P
Installation
Pressure line specifications:
the connected conduit.
The pressure line must be designed for at least 1.5 times the pump pressure.
Install the pressure line so that it rises continuously and is frost resistant.
Never connect other conduits to the pressure line.
Ventilation valves are not allowed in the pressure line.
The pressure line may not stand up in the special mounting adapter.
Ventilation line specifications:
Install the ventilation line up to above the roof. Ventilate connection lines longer than 5 m
separately.
If the inlet line above the system does not have a separate ventilation connection line longer
system.
grease separator can be used.