1) INSTALLATION INSTRUCTIONS
2) Thermal disinfection system for sanitary hot water installations
3) PRECAUTIONS FOR USE (The product guarantee depends on compliance with these instructions)
ASSEMBLY AND USE
For products delivered with filters, these must be installed in accordance with the instructions.
Before commissioning any of our valves, it is essential to carefully drain the pipes that can damage the mechanisms or water passages
(PRESTO® heads that can be dismantled from front).
CLEANING
The chrome-plated coating of PRESTO® valves must be cleaned only with soapy water.
Abrasive, acid, alkaline or ammonia-based household products are prohibited.
4) 1 USE
This system is designed to prevent and eliminate potential development of legionellosis in mixed water catchment points (40 °C).
The techniques used are thermal shock and/or regular rinsing of the installation to prevent water stagnation.
Thermal shock is performed for injecting hot water in the cold water system of catchment points (ideally 70°C) and the flow is automatically
managed by the system. A drain operation is also integrated to lower the temperature of catchment points in order to eliminate any risk of
burns after the disinfection cycle.
Stage
Action
no.
0
-
1
Actuation by rotating the key
clockwise
2
3
-
4
5
-
5) 1.1 THERMAL SHOCK:
For information, a thermal disinfection according to the "hot water" decree of 30 November 2005 is ensured by preheating:
60 min at 60°C
or 4 min at 65°C
or 2 min >= 70°C
These values can be adapted according to the installation. The disinfection and bleeding time flow are controlled by two time-flow relays
present in the control unit.
So that thermal shocks are as short as possible it is essential that the hot water temperature reaches at least 70 °C at the last catchment
point for several minutes.
The shock is activated through a key-operated switch on the control unit.
1.2 AUTOMATIC RINSING:
The automatic rinsing is not controlled by the control unit. However, it can be setup on the catchment points through sensitive buttons (see
"PLP shower panel" installation instructions).
1.3 SAFETY:
Thermal shocks must be performed by a competent person. All injuries relating to the activation of the system will be his own
responsibility.In case of a power failure, the system enables a mechanical return to the normal operating position (bypass off) and stops the
flow of the catchment points.
6) 2 CHARACTERISTICS
a. Control box with key switch overall dimensions 300*300*180mm
· Protection factor IP 65 (if all glands are shut-off).
· Power supply 230 V~ 50 Hz – 10 A.
b. Transformer 230/12 VAC-180VA.
c. 1 red indicator lamp indicating that disinfection is in progress
d. 1 orange indicator lamp indicating that bleeding is in progress
e. A control key that activates the disinfection by clockwise rotation and stops it by anti-clockwise rotation.
f. A disinfection time flow adjustable from 0.1s to 100h
g. A bleed time flow adjustable from 0.1s to 100h
h. Safety fuse T 1.25A – 250V
7) 3 INSTALLATION DIAGRAM
8) RED
9) BLUE
10) ORANGE
11) BLACK
12) White
13) D1: Shower 1
D10: Shower 10
14) Timer settings
15) Function selector (supplied respectively on functions Ln and Dr).
Adjustment in the selected range from 1 to 10.
Adjustment ranges from 0.1 sec to 10h.
16) For connection to shower panel, see instructions PLP Q434-7.
17) Hydraulic and Electrical connection
18) 4 INSTALLATION
The electrical and hydraulic connections must be made by qualified personnel taking the specification into account.
19) 4.1 FIXING THE CONTROL UNIT:
Fix the box attachment securely to the wall, see figures below. The cable gland outputs must point downward.
The control key must be easily accessible. Provide the distance needed to open the box attachment to the left,
see figure below.
Attachment dimensions (l X h) 300 x 300mm
20) Cable exit
21) 140cm from the ground
Cycle state
Normal operation
Disinfection
Red indicator lamp illuminated on the
Disinfection time delay
Bleed
Red indicator lamp Off + orange indicator
Bleed time delay
Normal operation
Orange indicator lamp Off
Indicator
_
front face of the box
lamp On
Catchment points
state
-
Bypass + Flow
Flow only
Flow stopped