6. Installation conditions
6 1
The model described in this manual is a component of a system and must be installed by authorised personnel only.
6.2
Access to the unit for any type of intervention must be reserved to personnel qualified to operate the system, in accordance
with the regulations in force.
6 3
The place of installation must conform to what is prescribed by local legislation.
6 4
The support structure must be suitable for the weight of the model in running condition (see Chapter 7)
6 5
This unit must not be installed in a potentially explosive or acidic atmosphere or in one that is not compatible with the
materials it is made of (copper, aluminium, steel, polymers).
6 6
Verify that the unit is installed horizontally.
6 7
The unit is not designed to act as a support for other machines or structures.
6 8
Avoid installation of the units next to the cold-room doors.
6 9
Ensure an adequate free space (approx. 30% of the inner room volume) to allow a proper intake and exhaust air
circulation. For the installation of more than one unit in the same cold or airconditioned room it is necessary to observe
the dimensions indicated in drawing. Keep the minimum distance so as to take out / insert the heaters.
AGD2
> 1.2 m
AGD3
2 : 4 m
> 3 m
5 : 8 m
Figure 3
B
B + 250
33