12.10 Cleaning of the finned pack:
AGS1
AGS3
AGS4
12.10.1 Place the main switch in the "OFF" position and wait until all the fans have stopped rotating. Lower the conveyor
(ref. Chapter 8). Protect the motor fans and electrical connections with waterproof covers and/or panels. If necessary,
remove the motor fans and their grilles by unscrewing the fixing screws.
12.10.2 Use compressed air at a maximum pressure of 10 bar and at a minimum distance of 150 mm, directed perpendicularly
against the finned pack to avoid bending or damage to the fins.
12.10.3 Use a jet of water at a max pressure of 50 bar for damp dirt or grease at a minimum distance of 150 mm, directed
46
www.modine.com
150mm
150mm
150mm
Figure 7
90°

Publicité