3 609 929 816/2009-02 | SBH.../SB...
6 Further Interfaces
6.2
Interfaces X4.1 / X4.2
Tightening systems, in which more than one
system box is used, are connected with the
BLxxx bus cables from the Rexroth supply
range. Up to a maximum of 16 system boxes
can be connected together. The bus lines are
plugged into the X4.2 and X4.1 interfaces.
The bus is to be closed off with AW300 ter-
mination resistors (consisting of AW301 +
AW302) on the first and last system box. The
AW301 is connected to the X4.1 interface
on the 1st box (the box with KE3x0).
The total line length of all bus lines used may
not exceed 100 m.
The X4.2 and X4.1 interfaces are only active
when a RK300 rack coupler is inserted into
each system box (see chapter 5).
SBH301
SB301
SB305
X4.1
X4.2
SBH301
SB301
SB305
X4.1
X4.2
Figure 20: Connection of several system boxes
KE3x0
Bosch Rexroth AG 49/148
6.2.1
Interface X4.1
3
2
1
Figure 21: X4.1 In Connector plug 8channel (male)
(Front view side of the system boxes)
Pin
Signal
Description/
Function
1
ARC1_A Serial
control bus +
2
ARC1_B Serial
control bus –
3
BA +
VCC_iso is
coupled using
diodes
4
GNDiso
Reference
potential external
5
GNDiso
Reference
potential external
6
ARC2_A Serial data bus + 5 V, RS485
7
ARC2_B Serial data bus – 5 V, RS485
8
n.c.
Table 10:
4
5
6
8
7
Voltage/
Current/
Standard
5 V, RS485
5 V, RS485