Adjustment of amperometric sensor sensitivity during slowing down in closing*
PSC
1: maximum sensibility - 99: minim sensibility
It is activated with AUX 1=2 parameter.
TLS
The activation time of the service light is adjusted.
It regulates the tension belt release when the operator arrives to the mechanical
SPIN
stop in closing
It selects the operating mode of the AUX 1 output:
0: Open gate indicator light. The light is off when the door is closed, flashes with
moving door and is on with open door.
See wire diagram.
1: Second radio channel. The output is controlled by the radio channel of the built-
AUX1
in receiver (see RADIO Menu).
2: Service light. The contact closes for the time preset with TLS parameter. The
countdown starts at the inception of the opening operation.
3: Area light. The contact closes in the opening phase and remains closed for the
entire TCA time. It opens only with closed door.
* ATTENTION: A wrong formulation of these parameters can be dangerous.
Respect the regulations in force!
MENU
Enables or disables automatic closing
TCA
On: automatic closing enabled
Off: automatic closing disabled
Enables or disables multi-flat function.
On: multi-flat function enabled. The step-by-step and perdestrian commands have
IBL
no effect during the opening phase.
Off: multi-flat function disabled.
During the TCA phase, the PP controls are enabled or disabled.
IBCA
On: PP controls are disabled.
Off: PP controls are enabled.
The rapid closure is enabled or disabled. It can be activated only if TCA:ON
On: enabled rapid closure. With open gate, the photocell activation causes the
automatic closure after 3 s.
SCL
If the photocell is activated during the opening phase, the operation is completed
and closure starts after 3s
Off: disabled rapid closure.
The operating mode of "P.P. Push button" and of the transmitter are selected.
PP
On: Operation : OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >
Forewarning flashing light enabled or disabled.
On: enabled forewarning flashing light. The flashing light is activated 3 s before the
PRE
starting of the motor.
Off: disabled forewarning flashing light.
During the TCA time, the blinker is enabled or disabled.
LTCA
On: Enables blinker.
Off: Disables blinker.
The code programmable transmitters is enabled or disabled.
On: Radio receiver enabled only for rolling-code transmitters.
CVAR
Off: Receiver enabled for rolling-code and programmable code transmitters (self-
learning and Dip Switch).
Soft start is enabled or disabled.
On: Starting is performed at reduced speed for 2s and then movement is restored
SOFT
to normal speed.
Off: Soft start is disabled.
The movement reversion during opening after the activation of the anti-crash
device (amperometric sensor) is enabled or disabled.
On: enabled reversion. The amperometric sensor activation causes the movement
INvA
reversion.
Off: disabled reversion. The amperometric sensor activation causes the movement
stop.
LOGICS (LOGI)
FUNCTION
1-99-(30%)
1-240-(60s)
0-20-(3)
0-3-(3)
DEAFULT
MEMO
(OFF)
(OFF)
(OFF)
(OFF)
(OFF)
(OFF)
(OFF)
(ON)
(ON)
(OFF)
15