SMA Solar Technology America LLC
Requirements:
☐ The technical requirements of the multifunction relay must be met (see Section 10 "Technical
Data", page 60).
☐ All electrical installations must be carried out in accordance with the local standards and the
National Electrical Code
Requirements for the conductors:
• Conductor cross-section: 0.2 mm² to 1.5 mm² (24 AWG to 16 AWG)
• The conductor type and wiring method must be appropriate for the application and location.
Procedure:
1.
Danger to life due to high voltages
• Ensure that the inverter is disconnected from all voltage sources (see Section 8, page 56
).
2. Remove the sealing plug from the enclosure opening on the multifunction relay.
3. Insert the conduit fitting into the opening and tighten from the inside using the counter nut.
4. Attach the conduit to the conduit fitting.
5. Guide the conductors from the conduit into the inverter.
6. Strip off the conductor insulation by max. 9 mm (0.35 in).
7. Connect the conductors to the plug according to
the circuit diagram, depending on the operating
mode (see Section 6.5.3, page 37). When
doing so, ensure that the conductors are
completely plugged into the conduit entries up to
their insulation.
8. Stick the plug into the MFR slot on the
communication assembly in the inverter.
9. Ensure that the plug is securely in place.
10. Ensure that all conductors are correctly connected.
11. Ensure that the conductors sit securely in the terminals.
Useful hint: To release the conductors from the plugs, open the conduit entries using a suitable
tool.