Commissioning
6.3.3 Analog output - ANALOG OUT/M3
All configurable parameters for the analog output can be found under the analog output menu
item which is marked as ANALOG OUT in the device.
!
Note!
This item is only available if the "Analog output" option is available in your device.
Function
(menu
item)
Ref. num.
Input
Lintab
Out damp
0..99.9
0.0
Out range
Off
0 - 20 mA
4 - 20 mA
0 - 10 V
2 - 10 V
0 - 1 V
Dec. point
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
Out 0%
-99999..99999
0.0
Out 100%
-99999..99999
100.0
Offset
-999.99..999.99
0.00
110
Parameter setting
Description
Selects which value is output at the analog output.
• Input = measured value
• Lintab = linearized measured value or current flow
value for channel calculation
Signal damping of measuring input with 1st order low
pass. Time constant can be selected from 0 to 99.9 sec.
Signal type of output
!
Note!
"Off" switches the output signal off completely.
Number of places after the decimal point for outputting
the measured value. Can be selected for analog signal
types
Start value of the output signal
End value of the output signal
Shifts the zero point of the output curve in mA or V.
RIA452