RIA452
Function
(menu
item)
Curve
Linear
Quad.
°C
°F
Kelvin
Damp
0..99.9
0
Dimension
XXXXXXXXX
%
Dec. point
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
0% value
-99999..99999
0
100% value
-99999..99999
100.0
Offset
-99999..99999
0.0
Comp. temp
Intern
const
Const. temp
9999.9
20.0
Open circ.
No
Yes
Endress+Hauser
Parameter setting
Description
Linear or quadratic (quad.) characteristic of the sensor
used. Can be selected for analog signals. °C, °F, Kelvin
physical measured variable, can be selected for
temperature sensors.
Signal damping of measuring input with 1st order low
pass. Time constant can be selected from 0 to 99.9 sec.
The technical unit or an arbitrary text for the measured
value of the sensor can be configured here. Max. length
9 characters.
Number of places after the decimal point for displaying
the measured value.
Start value of measured value, can be selected for
analog signal types
End value of measured value, can be selected for analog
signal types
Shifts the zero point of the response curve. This
function is used to adjust the sensor.
Comparative temperature for thermocouple
measurement. An internal cold junction (= Intern) or a
constant value (= const) can be selected.
Fixed comparative temperature.
This can only be selected if const is set for "Cmp.
Temp".
Switch cable open circuit detection for thermocouples
off or on
Commissioning
107