FAILURE OF THE THERMOSTAT FUSES AND REPLACEMENT
The installation and the electrical
connections of the units and their acces-
sories must only be carried out by peo-
ple possessing the technical/professional
requisites for system installation, trans-
formation, extension and maintenance,
and who are able to check these aspects
GLF10M
40
AGLF10NFJ 2006_5905145_04
for the purposes of safety and correct
operation. They will be generically
referred to in this manual as "Personnel
with specific technical skills". Check that
the power supply is disconnected before
carrying out any procedures on the unit.
If the fuses are burnt and for possible
replacement:
TYPE "A"
L
N
The fuses are 5 x 20 T series
230VAC
(delayed) from 2 A and 10 A
• WARNING: for correct replacement,
the 2 A fuse must be inserted in loca-
tion PF1, while the 10 A fuse must be
inserted in PF2, as shown in the image
230VAC
below.
PF2
• Remove the delivery frame
• Extract the thermostat card
• Open the thermostat box
• Replace the faulty fuses
VMF-SW1
The fuse 5 x 20 T series (delayed)
from 2 A
L
N
• WARNING: for correct replacement,
the 2 A fuse must be inserted in loca-
tion PF1.
PF1
TYPE "B"
PF1