Device configuration
Description of operating functions
The following table shows the menus available for the field indicator. These are explained in detail
in the sections specified.
Section
Section 7.1
Section 7.2
Section 7.3
Section 7.4
Section 7.5
7.1

Data processing (INPUT)

7.1.1
Input range
INPUT É CURVE É Options: Linear (LINAR) or square root (SQRT).
The input range is a 4 - 20 mA signal.
Select the type of input signal here (linear or quadratic).
7.1.2
Damping
INPUT É DAMP É Options: 0 - 99 (0 = no damping)
• Measured value damping can be set between 0 and 99 s.
• Only whole numbers can be entered.
• The factory setting is 0 (no damping).
®
2000 can be found in the online
Function
Data processing
Display
Limit values
Other settings
Service level
®