Mounting of jumpers
Montage des barres de pontage
Montaje de las pletinas de union
Jumpers
USED FOR
Barres de pontage
UTILISE POUR
Pletina de union
}
UTILIZADO PARA
27DC6011 / 27DC6021
27PV6011 / 27PV6021
2709X021
27DC8011 / 27DC8021
2709X024
27PV8011 / 27PV8021
2709X025
27DC6025 / 27DC8025
27PV6025 / 27PV8025
X = 0, 2 or 3
O
-
OFF
STEP 2
STEP 3
O
STEP 4
Horizontal mounting
Max. current
Cable
100A
3 AWG
200A
3/0 AWG
220A
4/0 AWG
250A
4/0 AWG
Vertical mounting
Max. current
Cable
100A
3 AWG
200A
3/0 AWG
220A
4/0 AWG
250A
250kcmil
2709 X021
2709 X024
5/6
-
OFF
Jumpers
2709 X021
2 x 2709 X021
2709 X024
2709 X025
Jumpers
2709 X021
2 x 2709 X021
2709 X024
2709 X025
2709 X025
X = 0, 2 or 3
STEP 1
O
-
OFF
Size 17
Torque
Couple
Par de apriete
lb-in
Nm
230
26
IS 541016-C