Installation and connection (continued)
4.2

Electrical connection

The BTL is connected via a S115 connector (see
Accessories on page 14).
PIN
Color
1
2
OG/WH Orange/
white
3
OG
Orange
4
5
GN/WH Green/white
6
BU
Blue
7
BN
Brown
8
GN
Green
Unassigned leads can be connected to the GND on the control side but
1)
not to the shield.
Reference potential for supply voltage and EMC-GND.
2)
Tab. 4-2:
Pin assignment of S115 connector
Fig. 4-4:
Pin assignment of S115 connector (view from above on
transducer plug)
8
english
BTL6‑V11V‑... interface
Not used
1)
Tx+
Tx-
Not used
1)
Rx+
GND
2)
+24 V
Rx-
4.3

Shielding and cable routing

Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect the transducer and controller using a shielded
cable.
Shielding: Copper filament braided, at least 85%
coverage
Horizontally connect the shield in the connector to the
plug housing.
Magnetic fields
The position measuring system is a magnetostrictive
system. It is important to maintain adequate distance
between the transducer and strong, external magnetic
fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible).
Cable length
The maximum cable length when using CAT5e cables is
100 m.