Technical Data; Manual Motor Starters - Eaton CROUSE-HINDS Série Mode D'emploi

Masquer les pouces Voir aussi pour CROUSE-HINDS Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Dimensions in mm
X = fixing dimensions
Wiring diagram
8
Manual motor starters up to 25 A, GHG 635
1

Technical data

1.1
Manual motor starters GHG 635
EC type examination certificate:
Marking acc. to 2014/34/EU:
*
Temperature class, see 1.6
IECEx certificate:
Category of application:
Rated voltage:
Rated current:
Short circuit back-up fuse:
AC 3 switching capacity:
Thermal tripping characteristic:
Short-circuit tripping as a multiple of rated current Ie:
Setting range 0.1 to 0,63 A
Setting range 0.63 to 2,5 A
Setting range 2.5 to 25 A
Tripping class:
Tripping time:
Perm.storage temperature in original packing:
(Other temperatures possible for special versions.)
Perm.storage temperature in original packing:
Degree of protection acc. to IEC/EN 60529:
Insulation class acc. to IEC/EN 61140:
Cabel entry:
0,1 A - 6,3 A
6,3 A - 25,0 A
with auxiliary contact / undervoltage release
Supply terminals:
Suitable cables and test torques
of the pressure screw
Cabel entry (KLE)
Seal 1+2+3
1 2
3
(Ø mm / Nm)
Seal 1+2
1 2
3
(Ø mm / Nm)
Seal 1
1 2
3
(Ø mm / Nm)
Test torque for screw in thread cable entry (Nm)
Cover screws:
Terminals (main contacts):
Terminals (auxiliary contacts):
Terminals (under voltage contacts):
Weight:
Standard design
with auxiliary contact / undervoltage release
(1) The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance work
on the cable entry..
PTB 99 ATEX 1162
II 2 G Ex d e IIC T5 / T6*
II 2 D Ex tD A21 IP66 T80° C
IECEx BKI 08.0014
IEC60079-0 Ex de IIC T5 / T6* Gb
Ex de IIC T55° C Db
690 V, 50/60 Hz / 440 V DC
up to 25 A
see point 1.4 and 1.5
690 V / 25 A
T II
7 .5 to 12-fold
8 to 14-fold
10 to 15-fold
10 A
see diagram 1, also point 1.7
-20° C up to +40° C (standard version)
-20° C up to +40° C
IP 66 (standard version)
I - with metal flange or metal cable glands
II - device fulfil this requirement
(standard version)
2 x M25
2 x M32
1 x M25 in addition
2 x 0.75 - 4.0 mm²
M20
M25
5.5 / 1.5
8.0 / 1.5
min.
(1)
7 .0 / 1.0
10.0 / 2.0
max.
7.0 / 1.5
10.0 / 2.3
min.
9.0 / 1.4
13.0 / 2.6
(1)
max.
9.5 / 1.0
13.5 / 1.3
min.
(1)
13.0 / 1.7
17 .5 / 2.3
max.
2.7
3.0
2.5 Nm
3.5 Nm
2.5 Nm
2.5 Nm
approx. 2.45 kg
approx. 2.55 kg
or
1 x 10 mm²
M40
M32
14.0 / 3.0
19.0 / 3.3
17.0 / 4.0
22.0 / 5.5
17.5 / 1.5
22.0 / 3.3
21.0 / 1.3
28.0 / 6.7
5.0
7 .5