10. Shutting down the unit

This section describes the procedure to shut down the unit. If it is necessary to carry out work on the unit interior
(qualified personnel only) these instructions must be followed in the same order shown here to remove the voltage.

10.1. Process of disconnecting the unit

In the event that you wish to shut down or disassemble the charging station, as a result of the auxiliary power
supply present in the unit it does not shut down directly after its power supply is removed. In this case the station
shows the following alarm message:
To completely shut down the station, identify a Master user card using the reader. Now the charging station can be
completely shut down.
It is strongly recommended to completely shut down the charging station in order to extend the life of
the auxiliary power supply.
56
"AC FAILURE"
ABA2020IQM01_A - Installation and Operation Manual