13. Shutting down the unit

This section describes the procedure to shut down the unit. If you wish to work inside the unit, you must carry out
these instructions in the order shown here to remove the power.
1.
If there is an active charge process, finalize the charge session.
2.
Press the emergency stop button.
3.
Remove AC voltage from a means of disconnection outside the unit.
4.
Wait 10 minutes for the internal capacitances to discharge, the hot parts which may cause burns to cool
and the fan blades to stop turning.
5.
Open the unit and, using the appropriate PPE, check the absence of voltage in the AC input.
6.
Signal cut-off point with a sign reading ¨Caution no switching...¨. If necessary, rope off the work area.
38
ABT2012IQM01_B- Installation and Operation Manual
Shutting down the unit