minimum enclosure clearances (GSS48STE - see through)

WARNING
!
Use only non-combustible materials (certified to ASTM E-136) such as steel studs, cement board, ceramic
tile, marble, paint, etc. When adding finishing materials to the appliance, do not use wood or drywall.
You must have clear and easy access to the on/off valve AFTER the appliance is installed and connected to
the gas supply in order to safely turn off the burner.
minimum to
60 3/4"
(1543mm)
minimum
to ceiling.
24 3/4" (629mm)
Including 1/8"
(3mm) clear-
ance per side.
(152mm)
minimum
to floor
note:
Ensure complete enclosure is closed
to prevent rain and debris from falling
on top of the appliance, as well as to
ensure no draft will occur through the
enclosure.
16
W415-3006 / A / 05.27.21
36"
(914mm)
ceiling.
6"
(152mm)
6"
(914mm)
minimum
to ceiling.
6"
(152mm)
minimum
to floor
NON COMBUSTIBLE
6"
6"
(152mm)
(152mm)
50 3/4" (1289mm)
(Including 1/8"
(3mm) clearance
per side)
36"
All material in
shaded area must
be Non Combustible
(including framing,
sheeting and
finishing materials).
Certified to ASTM
E-136
Nailing Tabs (4 per
side)
Gas and electrical lines protrude
from the bottom of the appliance
located on the right side.
21" (533mm) to
outside of steel
studs.
All material in shaded area must be
Non Combustible. (including framing,
sheeting and finishing materials).
Certified to ASTM E-136
Trim depth can be
altered depending
on finishing
material.