Room Controller 2 Configuration; Troubleshooting - Carrier CRC2 Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 15
NTC Room Controller 2
Room Controller 2 configuration, troubleshooting
Configuration table for NTC units
Item
Value
1-
°C
°F
2-
Co
St
3-
0
1
2
4-
0=0°C or 0°F
1=0,5°C or 0,9°F
2=1°C or 1,8°F
3=2°C or 3,6°F
5-
0
1
2
6-
0
1

Troubleshooting

Symptom
No LCD display
1) mis-wiring of the 12 volt
power to Room Controller 2 control.
2) Power not online
3) No 12 volts between P
and G of terminal block.
+12 volts applied to
1) The Room Controller 2
Room Controller at the
is damaged.
correct terminals and
still does not operate
The data sent by the
1) The connecting cable between
indoor unit are not
the unit to the Room Controller2 is
cut or not properly connected.
displayed.
Icon A is displayed.
1) Interference from another
There is no active
interface on the CRC2
button.
communication line.
GB - 6
Description
Temperatures displayed in degrees C
Temperatures displayed in degrees F
System
CRC2 will be used with a communicating system
Stand alone system
The CRC2 will be used with a non-communicating system
Temperature displaying
No temperature is displayed
The set-point temperature will be displayed
(In non-communicating systems the temperature range goes from
15 to 32 °C; from 59 to 90 °F)
(In non-communicating systems with Reset step 1°, the
temperature range goes from 18 to 26°C; from 68 to 76 °F)
(In communicating systems with Reset step 2°, the
temperature range goes from 16 to 30 °C ; from 64 to 80 °F)
The ambient temperature will be displayed
Reset Step Value
This represent the value of the single segment of the bar graph
One segment = 0° (C and F)
(In communicating systems with Reset step 0°, temperature is
fixed at 22 °C, 72 °F)
One segment = 1 °C or 0.9 °F
(In communicating systems with Reset step 0.5°, temperature
range goes from 18 to 26 °C; from 68 to 76 °F)
One segment = 1 °C or 1,8 °F
(In communicating systems with Reset step 1°, temperature
range goes from 18 to 26 °C; from 68 to 76 °F)
One segment = 2 °C or 3,6 °F
(In communicating systems with Reset step 2°, temperature
range goes from 16 to 30 °C; from 64 to 80 °F
Indoor fan icon displaying
The icon of the 3-speed indoor fan will not be displayed
The icon of the 3-speed indoor fan will be displayed
The variable speed indoor motor icon will be displayed
Louver icon displaying
The louver icon will not be displayed
The louver icon will be displayed
Possible Cause
Things to check
1) Verify that +12V and Ground are connected to the
proper terrminals of the Controller.
Reference Installation wiring section for correct
connections
1) Check that the units main power is connected. The
main control board should be operating normally
1) Check the installation of the J6 plug on the main
control board.
1) Check connection to J2 on the unit and on
CRC2 "I" connector.
1) Check that the LED card is connected.
Displayed
NO
NO
YES
NO
YES: Should the unit be provided
with variable speed indoor motor,
two speeds are available:
HIGH and AUTO.
YES
Solution
After disconnecting the power,
correct the wiring problem and
re-cycle power.
After verifing the wiring to the
Room Controller 2, re-cycle
the unit power.
After disconnecting the power,
correct the wiring problem and
re-cycle power.
Change the Room Controller
2 and re-cycle power.
After disconnecting the power,
correct the wiring problem and
re-cycle power.
Disconnect the LED card.
For Cassette units this should
be made by disconnecting the
black connector under the grille
filter.